8.3 Heating up the boiler
V Open the ash pan door.
V Turn the bolt [2] of the front grate counter-clockwise to
the stop.
V Fold the front grate [1] downwards.
Fig. 30 Folding the front grate downwards
1 Front grate
2 Bolt
V Turn the bolt [2] of the segment plate counter-clock-
wise to the stop.
V Remove the segment plate [1].
Fig. 31 Removing the segment plate
1 Segment plate
2 Bolt
V To increase the draft of the boiler, open the exhaust
flap.
Fig. 32 Open the exhaust flap
Warning: Risk of system damage due to in-
correct operation!
Overfilling the ignition chamber with fuel can
cause overheating and damage to the boiler.
V Adjust fuel quantity to the energy absorp-
tion of the heating system
(Æ Chapter 8.4, page 35).
Decisive for clean burning in the boiler are
the correct operation of the boiler and a suf-
ficient flue draft for the flue gas system.