Burner Spec Sheet

Table Of Contents
Carlin Burner Specifications - Buderus G215 Boilers Rev. 01/04
Boiler Burne
r
Flow Input Blast PSIG
A
i
r
Nozzle EZ-1 Head
A
pp
x
Overfire Breech
Model Model Rate Btu / Hr Tube Band D=Delavan Postion Bar Gross Press in. W.C. Pressure
GPH Insertion H=Hago Stack (base on breeching in. W.C.
Depth M=Monarch Temp° F
press shown) Ұ
DA=Danfoss
215-3 EZ-1HP 1.1 154,000 3 1/4" 150 0.85 D .85 60° B 0.85/1.0 305 Positive 0.06 -0.02
215-4 EZ-66 1.4 196,000 3 1/4" 150 50% H 1.10 45° ES Bar set @ 3 400 Positive 0.03 -0.02
215-5 EZ-66 1.7 238,000 3 1/4" 150 75% H 1.35 45° ES Bar set @ 5 400 Positive 0.05 -0.02
Riello Burner Specifications - Buderus G215 Boilers
Boiler Burne
r
Flow Input Blast PSIG
A
i
r
Nozzle Head
A
pp
x
Overfire Breech
Model Model Rate Btu / Hr Tube Band D=Delavan Setting Gross Press in. W.C. Pressure
GPH Insertion H=Hago Stack (Base on breeching in. W.C.
Depth M=Monarch Turbolator Temp° F press shown) Ұ
DA=Danfoss Setting
215-3 40-F5 1.1 154,000 3 3/4" 165 4 D .85 70° A 1 350 Positive 0.08 -0.02
215-4 40-F5 1.4 196,000 3 3/4" 150 4.75 D 1.20 60° W 4 350 Positive 0.06 -0.02
215-5 40-F10 1.7 238,000 3 3/4" 145 3.25 D 1.50 80° W 1.5 350 Positive 0.02 -0.02
215-6 40-F10 2.1 294000 3 3/4" 185 4.75 D 1.75 45° B 3 350 Positive 0.04 -0.02
215-7 40-F10 2.5 350,000 3 3/4" 160 5 D 2.0 80° B 3 350 Positive 0.10 -0.02
Beckett AFG Burner Specifications - Buderus G215 Boilers
Boiler Burne
r
Flow Input Blast PSIG
A
i
r
Nozzle Head
A
pp
x
Overfire Breech
Model Model Rate Btu / Hr Tube Band D=Delavan Setting Gross Press in. W.C. Pressure
GPH Insertion H=Hago Stack (base on breeching in. W.C.
Depth M=Monarch Temp° F press shown) Ұ
DA=Danfoss
215-3 AFG 1.1 154,000 3.5" 170 8/1* H .90 45° ES 0 300 Positive 0.065 -0.02
215-4 AFG 1.4 196,000 3.5" 175 8/2* H 1.10 45° ES 2 330 Positive 0.02 -0.02
215-5 CF375 1.7 238,000 3.5" 170 5/1* H 1.35 45° ES 2 387 Positive0.02 -0.02
215-6 CF375 2.1 294000 3.5" 140 7/2* H 1.75 45° ES 1 343 Positive0.09 -0.02
215-7 CF375 2.5 350,000 3.5" 150 9/3* H 2.0 45° P 1 316 Positive 0.13 -0.02
* Shutter/Band Settings. Blast tube insertion depth - Measured from tip of end cone to flange gasket.
Ұ Overfire pressure are measured at the measuring plug adjacent to the sight glass.
Set breaching pressure to -.02 to -.03 in. wc.
Above settings were established with baffles in place on the G215/3, G215/4 & G215/5 boilers. No baffles are furnished with the G215/6 and G215/7.
No baffles were used with the Riello Burner.
"ALWAYS KEEP THE MANUAL FUEL SUPPLY VALVE SHUT OFF IF THE BURNER IS SHUT DOWN FOR AN EXTENDED PERIOD OF TIME.
"

Summary of content (1 pages)