Installation Instructions

5
Installing the boiler
Logano G115 WS US/CA - Technical specifications are subject to change without prior notice.
26
5.8.2 Fitting temperature sensor assembly and burner cable
V Route capillary tubes and sensor wiring through the
cable opening of the front boiler jacket and connect to
test port.
V Roll up surplus capillary tubes and sensor lead and lay
them on the thermal insulation.
V Route the burner cable through the cable entry in the
front boiler cover to the control panel.
V Connect the burner cable to the control in accordance
with the terminal markings.
Fig. 22 Routing and connecting cables
1 Cable entry in the front boiler cover
2 Capillary tube and sensor cable
3 Immersion well (sensing point)
4 Burner cable
V Insert the temperature sensor assembly and balancing
spring in the immersion well and insert completely. The
plastic spiral is then pushed back automatically.
V Push the sensor retaining clip (supplied with the con-
trols) onto the top of the immersion well from the side.
Fig. 23 Fitting the temperature sensor assembly
1 Immersion well (sensing point)
2 Plastic coil
3 Balancing spring
4 Sensor retaining clip
Caution: Risk of system damage due to se-
vere kinking or sharp burrs on capillary tubes.
Capillary tubes can get damaged from se-
vere kinking or sharp burrs.
V Route capillary tubes carefully, avoiding
bending them excessively.
If a Beckett AquaSmart is being installed the
factory-fitted immersion well must be re-
placed by the immersion well supplied with
the control.
Ensure good contact between the sensor
surfaces and the sensor well to achieve accu-
rate readings. Use the balancing spring.
1
1
4
2
3
7 747 019 141-24.1RS