Installation Instructions

6
Commissioning the heating system
Logano G115 WS US/CA - Technical specifications are subject to change without prior notice.
29
6.3 Checking position of heat exchanger baffles
Prior to commissioning, check that the heat exchanger
baffles are in a horizontal position:
V Open burner door by removing the two hexagon-head
bolts at the sides.
V Slightly withdraw the flue gas baffles from the heat
exchanger.
V Adjust the heat exchanger baffles to a horizontal posi-
tion and push them back into the heat exchanger.
V Close burner door with the two hexagon bolts (approx.
90 inch-lbs). Tighten the hexagon bolts evenly to prop-
erly seal the burner door.
Fig. 27 Opening the burner door
1 Flue gas baffles in the heat exchanger
6.4 Preparing the heating system for operation
V Open the fuel supply at the main shut-off valve.
V Switch on the heating system emergency shut-off
switch and/or the appropriate circuit-breaker.
6.5 Starting up the control and the burner
For further start-up steps, follow the burner start-up
sequence.To do so, it is essential that you consult the
burner Æ documentation.
Use the on/off switch on the controls to switch the heat-
ing system on. The burner starts up if the system is calling
for heat or if you set the controls to manual mode.
Æ service instructions for the controls.
V Select "Manual" mode .
V Set the boiler water temperature control to the desired
temperature.
V Switch the on/off switch on (position "I").
Fig. 28 Switching on the controller
(e. g. Logamatic 2000)
1 Boiler water thermostat
2 On/off switch
1
7 747 019 141-27.1RS
1
2
7 747 019 141-28.1RS