8.3 Cleaning the boiler
The boiler can be cleaned with brushes and/or by a wet
method. Cleaning equipment is available as accessory.
V Open burner door by removing the two hexagon bolts
on the sides.
8.3.1 Cleaning the boiler with brushes
V Note the position of the heat exchanger baffles for later.
V Remove the hot gas baffle plates from the hot gas pas-
sages.
V Clean the hot gas baffle plates with one of the two
cleaning brushes.
Fig. 36 After opening the burner door
1 Flue gas baffles in the heat exchanger
V Clean the hot gas passages by turning the round clean-
ing brush.
Fig. 37 Brushing out the hot gas flues
V Clean the combustion chamber with a flat brush.
Remove the debris from the combustion chamber, the
hot gas flues and the flue connection.
V Refit the heat exchanger baffles in their original posi-
tions.
V Check sealing rope on burner door. Replace damaged
or hardened gasket cord.
V Close burner door with the two hexagon bolts (approx.
90 inch-lbs). Tighten the hexagon bolts evenly.
Fig. 38 Brushing out the combustion chamber
Caution: Risk of burning by touching hot
boiler parts.
V Wear appropriate protective personal
safety equipment.
1
7 747 019 141-27.1RS
7 747 019 141-37.1RS
You can obtain suitable gasket cord from
your local Buderus sales office.
7 747 019 141-38.1RS