Installation Instructions
8
Heating system servicing
Logano G115 WS US/CA - Technical specifications are subject to change without prior notice.
37
8.3.2 Wet cleaning (chemical cleaning)
For wet cleaning use a cleaning agent appropriate for the
degree of soiling (soot or scale). Proceed with the wet
cleaning in the same order as described for cleaning with
brushes (Æ Chapter 8.3.1, page 36).
V Cover the control panel with plastic to prevent spray
from entering the control panel.
V Spray cleaning agent evenly into the heat exchanger
heater passages.
V Close burner door and start up the heating system.
V Heat the boiler to a temperature of at least 160 °F.
V Shut down the heating system.
V Brush out the heat exchanger heater.
8.4 Checking heating system operating pressure
The system pressure for closed systems must be
15 – 30 psi (1.0 – 2.1 bar).
V Check system pressure.
V If the pressure gauge shows less than 15 psi, the pres-
sure is too low. Top up the system with water.
Fig. 39 Pressure/temperature gauge for showing oper-
ating pressure and feed temperature
Follow the instructions for the cleaning prod-
uct. You may need to proceed differently
from the method described here in some cir-
cumstances.
Caution: Risk of system damage due to fre-
quent topping up.
If you have to top up the heating water fre-
quently, the heating system may suffer dam-
age from corrosion or scaling, depending on
the water quality.
V Ensure that your heating system is bled
properly.
V Check the heating system for leaks and
proper operation of the expansion vessel.
7 747 019 141-17.1RS