Installation Instructions
12
Circuit diagrams
Logano G115 WS US/CA - Technical specifications are subject to change without prior notice.
51
Fig. 48 Circuit diagram 2
Carlin EZ-1 HP Burner Wiring with L7248C Aquastat
T
B1
Honeywell
Operating
Aquastat
(L7248C1006)
Carlin EZ-1 Wiring Schematic -
The Carlin EZ-1 Burner is equipped with the 60200 Series Primary Control with pre-purge.
Using a L7248C Aquastat –
1) Connect room thermostat or end switch wiring to the T & T terminals of the L7248C Aquastat.
Note: DO NOT CONNECT ROOM THERMOSTAT TO THE T – T TERMINALS OF THE CARLIN 60200 Control!
2) Connect 120 Vac power source to L1 on the L7248C aquastat.
3) Connect neutral source to L2 on the aquastat.
4) Connect red wire from wire harness to L1 on the L7248C (the red/white wire on the Carlin 60200 Control).
5) Connect black wire from wire harness to B1 on the L7248C (the black wire on the Carlin 60200 Control).
6) Connect white wire from wire harness to B2 on the L7248C ( the white wire on the Carlin 60200 Control).
7) Connect green wire to ground screw on the L7248C and to the ground connection on the Carlin Burner.
8) Install a jumper wire on the T T terminals of the 60200 Control.
9) The pink wires from the Carlin “In line heater” may be connected to a constant 120Vac power source or the red/white wire and the white wire
in the Carlin 60200 Primary Control.
CCT 60200 Series Primary Control
Field
installed
jumper
Field wiring
Factory wired
Low Voltage
Field installed
Quick
connect
plug
White
Violet
Orange
Blue
Red/White
Black
T
F
T
F
A
A
CAD
Cell Eye
Red wire
Black wire
White wire
Green wire
Ground
Ground
T
Thermostat,
aquastat, or end
switch,
C1
C2
L1
B2
L2
Fuse
Service
Switch
N
Neutral
L
Hot
WMO-1*)
*) Canadian installations: Install in series with start wire to the burner (phase).