Technical Information Logamatic LON-Gateway- Subject to modifications resulting from technical improvements!
13
Network interface
3
Boiler 1
47 Status of burner boiler 1
1)
SNVT_state(83) nvoKS1Br1Stufe1
48 Status burner boiler 1 SNVT_state(83) nvoKS1Br1Stufe2
49 Display boiler actual temperature SNVT_temp_p(105) nvoKS1VLIst_Tp
Boiler 2
50 Status burner boiler 2
1)
SNVT_state(83) nvoKS2Br1Stufe1
51 Status burner boiler 2 SNVT_state(83) nvoKS2Br1Stufe2
52 Display boiler actual temperature SNVT_temp_p(105) nvoKS2VLIst_Tp
Solar thermal system
53 Change operating mode (D/N/A) SNVT_hvac_mode (108) nviSLTgNtAt
54 Display operating mode (D/N/A) SNVT_hvac_mode (108) nvoSLBetrieb
55 Display collector actual temperature (FSK) SNVT_temp_p(105) nvoSLKoll_Tp
56 Display solar tank actual temperature (FSS1) SNVT_temp_p(105) nvoSLSP1Unten_Tp
57 Display solar yield (heat quantity) SNVT_elec_kwh_l (146) nvoSLWMZ_Ertrag
58 SNVT_file_pos(90) nviParameter
59 SNVT_file_pos(90) nviAdresse
60 SNVT_file_pos(90) nvoMonitoring
1) Display of the output for boilers with Logamatic EMS
No. Meaning SNVT type SNVT name