Operating Instructions

Network interface
Technical Information Logamatic LON-Gateway- Subject to modifications resulting from technical improvements!
32
3
3.4.4 Strategy
In the "Strategy" section, the values for the entire heating system are summarized. This is especially
important for multi-boiler systems (cascades).
Format:
Changing the operating mode
With the HVAC_heat / HVAC_off setting, the operating mode for the consumer is changed
externally via the LON data bus.
Set range: 32 °F to 194 °F (0 °C to 90 °C); in 1-degree intervals
Note:
230 °F (110 °C) is an invalid value (e.g. no temperature sensor connected, sensor defective, etc.).
Note:
230 °F (110 °C) is an invalid value (e.g. no temperature sensor connected, sensor defective, etc.).
Note:
230 °F (110 °C) is an invalid value (e.g. no temperature sensor connected, sensor defective, etc.).
23 Operating mode (D/N/A) system SNVT_hvac_mode (108) nviAnl_TgNtAt 2
Tab. 68 Value for changing the operating mode of the entire system (all heating zones)
Value Designation Description
0HVAC_AUTO
The system works according to the internal setting on the control panel (automatic mode).
1 HVAC_heat The system is turned on (all on) and works in manual day mode.
6 HVAC_off The system is turned off (all off).
24 System supply set point
temperature
SNVT_temp_p(105) nviAnlVorgabe_Tp 2
Tab. 69 Value for changing the system set point temperature (boiler supply temperature)
25 System supply set point
temperature
SNVT_temp_p(105) nvoAnlVLIst_Tp 2
Tab. 70 Display of the currently-valid set point temperature for the boiler system
26 System supply actual
temperature
SNVT_temp_p(105) nvoAnlRLIst_Tp 2
Tab. 71 Display of the currently-measured supply temperature for the boiler system
27 System return actual
temperature
SNVT_temp_p(105) nvoAnlRLIst_Tp 2
Tab. 72 Display of the currently-measured return temperature for the boiler system