Operating Instructions
Table Of Contents
- Contents
- 1 Explanation of symbols and safety instructions
- 1.1 Guideline to symbols
- 1.2 Safety instructions
- 2 Product description
- 3 Network interface
- 4 Operating basics
- 5 Incorporation of Logamatic 4000 in LON networks via Logamatic LON-Gateway
- 6 The LON-Gateway as LonMark object
- 7 Error list
Technical Information Logamatic LON-Gateway- Subject to modifications resulting from technical improvements!
35
Network interface
3
3.4.6 Boiler 2
This section describes "boiler 2." For boilers 3 and 4, the details apply accordingly.
Burner OFF [0 %]
ON [> 0 %]
Current output [%]
Note:
230 °F (110 °C) is an invalid value (e.g. no temperature sensor connected, sensor defective, etc.).
Pump OFF [0 %]
ON [> 0 %]
Current output [%]
38 Status burner boiler 2 SNVT_lev_cont (21) nvoKS2_BrStatus 1
Tab. 83 Indicator for boiler with Logamatic EMS or 4000
39 Temperature boiler 2 (FK) actual SNVT_temp_p(105) nvoKS2VLIst_Tp 2
Tab. 84 Display of the current boiler temperature for boiler with Logamatic EMS or 4000
40 Boiler hours of operation 4000
boiler 2 level 1
SNVT_time_hour(124) nvoKS2Br4000S1_h 2
Tab. 85 Display of the hours of operation for the level 1 (basic load) of boiler with
Logamatic 4000 and third party burner
41 Boiler hours of operation
4000 boiler 2 level 2
SNVT_time_hour(124) nvoKS2Br4000S2_h 2
Tab. 86 Display of the hours of operation for the modulation/level 2 (large load) of boiler with
Logamatic 4000 and third party burner
42 Pump 4000 boiler 2 SNVT_lev_cont (21) nvoKS2PU_4000 1
Tab. 87 Operating message for the boiler circulation pump of the boiler with Logamatic 4000
and third party burner
43 Burner hours of operation EMS
boiler 2
SNVT_time_hour(124) nvoKS1Br_EMS_h 2
Tab. 88 Display of the hours of operation for boiler with Logamatic EMS










