Operating Instructions

Technical Information Logamatic LON-Gateway- Subject to modifications resulting from technical improvements!
37
Network interface
3
3.4.7 Status
Using the feedback from the Logamatic control panels, you can get information about whether
control panels were turned off, etc.
Status "1" means Logamatic controls are present on the ECOCAN-BUS.
Status "0" means Logamatic controls are not present on the ECOCAN-BUS.
Example:
In this example, Logamatic controls are connected to the ECOCAN-BUS addresses 1, 2, and 3.
With this variable, information about the LON-Gateway is output.
"CAN V. XX.YY" indicates the firmware version of the LON-Gateway.
"LON V.XX.YY" indicates the software version of the LON-Gateway (XIF file).
59 Status ECOCAN-BUS SNVT_state(83) nvo_CAN_Adressen 2
Tab. 90 With these variables, a status report of the ECOCAN-BUS is transmitted to LON
Logamatic controls First byte Second byte
Address (ECOCAN-BUS)01234567 89101112131415
Status 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Logamatic controls First byte Second byte
Address (ECOCAN-BUS)01234567 89101112131415
Status 0 1 1 1 0 0 0 0 0 0 0 0 0 0 0 0
60 Status LON version SNVT_str_asc (36) nvo_LONVersion 31
Tab. 91 Information display via the LON-Gateway
123456789111111111122222222223
0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
C A N . x x . y y / L O N L . x x . y y