Operating instructions
System settings (Service menu – Settings)
Logamatic EMS RC35 programming unit - Subject to technical modifications
24
6 
6.1.1 Building type (adjusting the outside temperature)
A building's heat storage capacity and its characteristic resistance to heat transfer will delay the 
effect of outside temperature fluctuations on the rooms inside. Consequently, it is not the current 
outside temperature that is crucial but the so-called adjusted outside temperature. 
Parameter building type enables the adjustment to be applied that takes account of the fluctuating 
outside temperatures. This enables the control to be matched to the characteristics of the building.
The control unit calculates the time constant for adjusting the outside temperature, using the factor 
given in Tab. 10 for the stated building type and an internal multiplier, the “runtime” (= 6 minutes). 
The time constant is the product of: factor x runtime = adjustment time constant in hours.
Should the outside temp. damping 
be switched off?
yes, no no When selecting “yes” the following 
parameter building type will be 
hidden.
What type of building do you 
have?
light,
medium, 
heavy
medium Building type (heat storage 
capacity), Æ Chapter 6.1.1, 
page 24.
What is the lowest expected 
outside temp. in your region?
– 30 °C to 
0°C
– 10 °C Æ Chapter 6.1.2, page 25
1) Not possible or available on boilers with UBA1.x or DBA.
2) Not possible on boilers with UBA4.
3) Only possible on boilers with UBA4.
Parameter: 
building type
Type of construction Factor
light E.g. prefabricated building, wood-frame construction 10
medium E.g. a building constructed of hollow breeze blocks (factory 
setting)
30
heavy E.g. brick house 50
Tab. 10 Calculating the adjustment time constant
Menu item
Input 
range
Factory 
setting Other information
Tab. 9 Navigator for service menu SETTINGS\SYSTEM