Operating instructions
System settings (Service menu – Settings)
Logamatic EMS RC35 programming unit - Subject to technical modifications
28
6 
Heating curve
std. tmp. ( – 10 °C) 30 °C to 90 °C 75 °C 
(radiator, 
convector) 
45 °C 
(floor)
The value in brackets is the setting 
for the minimum outside temperature 
(Æ page 27). Adjustment only if the 
control type is set to “outside temp. 
contr.” ( Æ page 32).
max flow temp. radiator, 
convector: 
30 °C to 90 °C
1)
floor:
30 °C to 60 °C
radiator, 
convector: 
75 °C
floor: 50 °C
Adjustment only if the control type is 
set to “outside temp. contr.” 
( Æ page 32).
Enter the maximum 
flow temperature:
Adjustment only if the control type is 
set to “room temp. contr.” 
( Æ page 32).
min flow temp. 5 °C to 70 °C 5 °C Adjustment only if the control type is 
set to “outside temp. contr.” 
( Æ page 32).
Enter the minimum flow 
temperature:
Adjustment only if the control type is 
set to “room temp. contr.” 
( Æ page 32).
rm. tmp. offset – 5.0 K to +5.0 K 0.0 K Offset of heating curve.
Adjustment only if the control type is 
set to “outside temp. contr.” 
( Æ page 32).
Enter the maximum room 
influence: 
0 K to 10 K 3 K Adjustment only if the control type is 
set to “outside temp. contr.” 
( Æ page 31)
Which type of reduction 
should be implemented?
Outdoor setback 
mode, 
reduced operation, 
Room setback 
mode (only if 
RC35 or RC2x has 
been assigned to 
the heating circuit), 
shut-down mode
Outdoor 
setback 
mode
Night setback (Æ page 33)
Menu item Input range
Factory 
setting Other information
Tab. 12 Navigator for service menu SETTINGS\HTG. CIRC. 1