Operating instructions
Troubleshooting
Logamatic EMS RC35 programming unit - Subject to technical modifications
52
10 
A18 825 Two master 
operating 
units in 
system.
RC35 and RC2x 
regulate both heating 
circuits and DHW. 
Subject to the 
selected heating 
programs and the 
required room 
temperature, the 
heating system may no 
longer function 
correctly.
DHW heating is mal-
functioning.
RC2x and RC35 are 
both logged on as 
master.
B Change parameter 
P1 in RC2x or 
remove RC35 from 
the EMS BUS.
A2x 806 Room 
temperature 
for HCx is 
defect.
Since the actual room 
temperature is 
missing, the following 
cannot function:
• Room influence (for 
weather-
compensated 
control)
• Switching point 
optimisation
In the case of room 
temperature-
dependent control, the 
system is regulated to 
max. temperature for 
HCx.
Faulty integral 
temperature sensor on 
the heating circuit's 
programming unit / 
remote control unit.
B Replace the remote 
control unit.
A2x 816 No commu-
nication with 
operating 
unit HCx.
Since the actual room 
temperature is 
missing, the following 
cannot function:
• Room influence
• Switching point 
optimisation
RC2x incorrectly 
addressed, wired or 
faulty.
Heating circuit has not 
been registered on the 
RFM20.
B Check address in 
RC2x.
B Check function and 
connection of the 
remote control unit.
B Replace the remote 
control unit.
SC FC
Events 
display
Effect on control 
characteristics Possible cause Remedy
Tab. 21 Fault table