Troubleshooting guide

19
e Ground Fault Circuit Interrupter
(GFCI) is an important safety device and
is required equipment on a hot tub instal-
lation.
Used for verifying a proper installation
e GFCI Trip Test must occur to allow
proper spa function. Within 1 to 7 days
after startup, the spa will trip the GFCI
to test it. (e number of days is factory
programmed.) e GFCI must be reset once it has tripped. After passing the
GFCI Trip Test, any subsequent GFCI trips will indicate a ground fault or
other unsafe condition and the power to the spa must be shut o until a
service person can correct the problem.
Forcing the GFCI Trip Test (North America Only)
e installer can cause the GFCI Trip Test to occur sooner by initiating it
using the above menu. e GFCI should trip within several seconds and
the spa should shut down. If it does not, shut down the power and manually
verify that a GFCI breaker is installed and that the circuit and spa are wired
correctly. Verify the function of the GFCI with its own test button. Restore
power to the spa and repeat the GFCI Trip Test. Once the GFCI is tripped
by the test, reset the GFCI and the spa will operate normally from that
point. You can verify a successful test by navigating to the above menu. PASS
should appear after a temp button is pressed from the GFCI screen.
Warning:
If freezing conditions exist, the GFCI should be reset immediately or spa
damage could result.
Utilities- GFCI Test Feature
The Ground Fault Circuit Interrupter (GFCI) is an important
safety device and is required equipment on a hot tub
installation.
Used for verifying a proper installation
The GFCI Trip Test must occur to allow proper spa function.
Within 1 to 7 days after startup, the spa will trip the GFCI to test
it. (The number of days is factory programmed.) The GFCI must
be reset once it has tripped. After passing the GFCI Trip Test, any
subsequent GFCI trips will indicate a ground fault or other unsafe
condition and the power to the spa must be shut off until a
service person can correct the problem.
Forcing the GFCI Trip Test (North America Only)
The installer can cause the GFCI Trip Test to occur sooner by initiating it using the above menu.
The GFCI should trip within several seconds and the spa should shut down. If it does not, shut down the power and
manually verify that a GFCI breaker is installed and that the circuit and spa are wired correctly. Verify the function of the
GFCI with its own test button. Restore power to the spa and repeat the GFCI Trip Test.
Once the GFCI is tripped by the test, reset the GFCI and the spa will operate normally from that point. You can verify a
successful test by navigating to the above menu. PASS should appear after a temp button is pressed from the GFCI screen.
Warning:
If freezing conditions exist, the GFCI should be reset immediately or spa damage could result.
Utilities – GFCI Test Feature
GFCI Status - Passed
Back
Test
Reset