Service and Repair Manual

11
C. TORSION SPRINGS
WEAK TORSION SPRINGS
T
DAMAGED/WORN BUSHINGS/SEALS
TOO MUCH KRYTOX GREASE
CHILL MODE
NORMAL OPERATION
POSSIBLE CAUSES FOR FALSE READINGS
ICE MODE
BENT TORQUE SENSOR PINS
D. AUGER SHAFT
A. MOTOR SHAFT TORQUE SENSOR PIN
B. AUGER SHAFT TORQUE SENSOR PIN
E. AUGER MOTOR COUPLING
C
D
B
A
E
PREVENTIVE MAINTENANCE
A common problem occurs when the proper preventive maintenance procedures are not followed. Failure to
perform these procedures may result in damaged equipment and may not be covered by warranty.
Please check the following items before assuming a refrigeration fault.
When the product does not freeze, there are several possibilities other than a failure in the refrigeration system.
The torque between the auger motor and the frozen product is contolled by the torque sensor board measur-
ing the distance between the pins on the coupler and shaft. When the distance between the pins reaches the
maximum allowable distance, the compressor shuts off. The machine thinks the product thickness has reach
the maximum and shuts off the compressor. The illustration below shows some of the other possible causes for
a false reading from the torque sensor board.
Proper inspection and preventive maintenance (including daily cleaning) will avoid expensive repairs and costly
down time.
41084 102709