Installation and Operating Guide

17
LEVEL 2 PROGRAMMING
H1 - DISPENSE LOCKOUT
1. To enter Level 2 Programming, press and hold the
hidden
button until H1 ap-
pears on the display. Release the
hidden
button. The display will show “noL” (no
lockout) or Loc (dispense lockout).
2. Press and release the (+) or (-) buttons to alternate between noL and Loc.
H2 - C° OR F° SELECTION
1. To enter Level 2 Programming, press and hold the
hidden
button until H1 appears
on the display. Press and release the
hidden
button. The display will show CEn
(Degrees in Centigrade) or FAH (Degrees in Fahrenheit)
2. Press and release the (+) or (-) buttons to alternate between FAH and CEn.
H3 - RESTORING FACTORY DEFAULTS
1. To restore Factory Defaults (This clears all settings that were previously entered),
press and release the
hidden
button until H1 appears on the display. Press and
release the
hidden
button, then press and release the
hidden
button once more.
The display will read H3, then show (- - -).
2. Press and hold both (+) and (-) buttons to initiate the resetting of the factory
default settings. The display (- - -) will flash on and off during this time.
3. When the factory default numbers are loaded in, the display will stop flashing,
then read don (DONE). You can now release the two buttons.
NOTE: If you release the two buttons at any time before the display reads don, the Fac-
tory Default numbers will not be entered. The old numbers will remain in the memory.
PROGRAMMING - H3E ELEMENT Continued
46819.1 070215