Owner's manual
1066 - 9
TECHNICAL DATA
english
Options
Number of pilot valves
Control heads without communication
8-pole screw terminal for 24 V DC
Multipol (8-pole round plug) for 24 V DC
2 x 6 screw terminals for 24 / 110 / 230 V UC
Control heads with communication
Actuator sensor interface (ASI)
DeviceNet
ATTENTION!
The connection to other (higher) bus systems is possible using commercially available
Gateways.
Operating conditions
Media Compressed air, non-oiled; neutral gases
Medium temperature -10 ... + 50 °C
Ambient temperature -10 ... + 50 °C
Protection class IP 67
Mechanical data
Weight 0.5 bis 0.65 kg (depending on model)
Housing material Housing PA / PPE
Cover PSU (transparent, blue-grey)
Sealing material NBR
ATTENTION!
The control head is not suitable for use outdoors!
Operating mode / Type of application Number of pilot valves
Single-acting actuators 1
Double-acting actuators 2
Dual-seat valves with integrated air supply to both valve seats 3