INSTALLATION AND COMMISSIONING
english
II. ASI version with extended address range (A/B Slave)
1 Master can communicate with 62 Slaves with the ASI version with extended address range (A/B Slave).
As in the standard case, the bus cable with extended address range according to ASI specifications my be
a maximum 100 m long.
ATTENTION!
If an A/B Slave device is being used as a replacement for a standard device, a
configuration error arises due to the different ID codes!
Differences in the addressing of ASI variants
Parameters ASI Standard device ASI device for A/B Slave addressing
Number Slaves / Master 31 62
I/O Code 7 hex 7 hex
ID Code F hex A hex
Extended ID1 F hex 7 hex
Extended ID2 F hex E hex
Profile S-7.F.F S-7.A.E
Characteristics of the A/B Slave variant compared with the standard case
62 Slaves per Master
The yellow OUT 4 LED on the ASI circuit board is no longer controllable, since the fourth output bit
used up to now is now used for the addressing.
Limitations in power supply due to the nominal current of the inductors:
Only 2 solenoid valves can be connected at the same time; the third solenoid valve can only be
hooked up after 100 ms have passed.
NOTE
Maximum cable lengths also vary when other cable cross sections are used (see ASI
specifications).