Operating Instructions Bedienungsanleitung Instructions de Service Type 1150 Process and Program controller
We reserve the right to make technical changes without notice. Technische Änderungen vorbehalten. Sous resérve de modification techniques. © 2004 Bürkert Werke GmbH & Co.
CONTENTS Table of Contents Process and Program Controller Type 1150 GENERAL NOTES ................................................................................................................................................................................................................................. 5 Typographical conventions ..............................................................................................................................................................................
CONTENTS ELECTRICAL CONNECTIONS ................................................................................................................................................................................ 21 Connection diagram ............................................................................................................................................................................................................ 22 Terminal Strip Numerical Assignment .....................................
CONTENTS OPTIMIZATION ..................................................................................................................................................................................................................................... 85 Self-optimization ....................................................................................................................................................................................................................... 86 Oscillation method .
CONTENTS 4 - 1150
GENERAL NOTES GENERAL NOTES Typographical conventions ............................................................................................................................................................................................ 6 Safety instructions ...................................................................................................................................................................................................................
GENERAL NOTES Typographical conventions Symbols Indicates procedure(s) that you must carry out. ATTENTION! NOTE CAUTION! Indicates information, where failure to observe, your safety or the proper function of the device will be compromised. Indicates important additional information, tips and recommendations. This device is sensitive to electrostatic discharge (ESD). Contact with an electrically charged personnel or object will damage this device.
GENERAL NOTES Protection from damage by electrostatic charging This device contains electronic components that are sensitive to electrostatic discharge (ESD). Contact with electrostatically charged persons or objects will damage these components. In the worst case, they will be immediately destroyed or will fail after commissioning. Observe the requirements of EN 100 015 - 1 in order to minimize the possibility of, or avoid, damage from instantaneous electrostatic discharge.
GENERAL NOTES 8 - 1150
SYSTEM DESCRIPTION SYSTEM DESCRIPTION Function description .............................................................................................................................................................................................................. 10 Technical data ...............................................................................................................................................................................................................................
SYSTEM DESCRIPTION Function description Type 1150 is a process and program controller with up to four controller or program channels. The instrument is built to the format 144 mm x 130 mm for a standard 92 mm x 92 mm panel cut-out and a mounting depth of 170 mm. The display is a 5" color screen with 27 colors. The layout of the screen templates can be individually adapted and adjusted.
SYSTEM DESCRIPTION Visual Representation Technical data Thermocouple input Designation Fe-CuNi "L" Fe-CuNi "J" Cu-CuNi "U" Cu-CuNi "T" NiCr-Ni "K" NiCr-CuNi "E" NiCrSi-NiSi "N" Pt10Rh-Pt "S" Pt13Rh-Pt "R" Pt30Rh-Pt6Rh "B" W5Re-W26Re "C" W3Re-W25Re "D" W3Re-W26Re Meas.
SYSTEM DESCRIPTION Input for standard signals Designation Measurement range Voltage 0 to 10 V -10 to +10 V -1 to +1 V 0 to +1 V 0 to 100 mV -100 to +100 mV Input resitance R E Current 4 to 20 mA, voltage drop 0 to 20 mA, voltage drop Heater current 0 to 50 mA AC Potentiometer min. 100 1 Meas. accuracy 1 0.05 0.05 0.05 0.05 0.05 0,05 % % % % % % Ambient temperature error 100 100 100 100 100 100 ppm/K ppm/K ppm/K ppm/K ppm/K ppm/K 100 k 1V 1V 0.1 % 0.
SYSTEM DESCRIPTION Controller Controller type single-setpoint controller double-setpoint controller, modulating controller, proportional controller, proportional controller with integrated actuator driver Controller structures P/PD/PI/PID/I A/D converter dynamic resolution up to 16 Bit Sampling time 250 msec 50 msec, 150 msec, 250 msec (configurable) Color screen Resolution Size (screen diagonal) No. of colors 320 x 240 pixels 5" (12.
SYSTEM DESCRIPTION Housing Housing type housing and back panel: metal for panel mounting as per DIN 43700 Front bezel plastic to UL 94 V0 144 mm x 130 mm Mounting depth 170 mm Panel cut-out 92+ Ambient/storage temperature range 0,8 x 92+0,8 mm -5 to 50 °C / -40 to +70 °C Climatic conditions rel. humidity 75 % annual mean, no condensation Operating position horizontal Enclosure protection to EN 60 529, front IP 65, rear IP 20 Weight (fully fitted) approx.
SYSTEM DESCRIPTION Order table Process and program controller Type 1150 ID-No. Basic unit 20 to 30 V AC/DC 787703 110 to 240 V 48 to 63 Hz 787704 Input modules 1 analog input 787750 Output modules 1 relay, changeover 787751 1 solid-state relay 787752 2 relay, n.o.
SYSTEM DESCRIPTION 16 - 1150
INSTALLATION, COMMISSIONING AND MAINTENANCE INSTALLATION, COMMISSIONING AND MAINTENANCE General notes ............................................................................................................................................................................................................................. 18 Location and climatic conditions .......................................................................................................................................................
INSTALLATION, COMMISSIONING AND MAINTENANCE General notes ATTENTION! • This device should only be installed or repaired by qualified personel using the correct tools! • Always disconnect the power this device before servicing or changing signal connections! • Failure or interference may result from contamination, short circuit, voltage interruption or faulty/missing wiring termination. • Check for loose or improper electrical connections or under voltage if unit does not power up.
INSTALLATION, COMMISSIONING AND MAINTENANCE Installation ATTENTION! Please observe the relevant safety regulations and electrical installation codes for your area. • The choice of cable - the installation and the electrical connection must conform to the requirements of VDE 0100 “Regulations on the Installation of Power Circuits with Nominal Voltages below 1000 V” or the appropriate local regulations. • The electrical connection may only be carried out by properly qualified personnel.
INSTALLATION, COMMISSIONING AND MAINTENANCE Accessories PC Interface PC interface for setup program Setup programs Setup program with program editor Maintenance Cleaning The front panel can be cleaned with normal commercial washing, rinsing and cleaning agents. It has a limited resistance to organic solvents (e.g. methylated spirits, white spirit, P1, xylol etc.). Do not use highpressure cleaning equipment.
ELECTRICAL CONNECTIONS ELECTRICAL CONNECTIONS Connection diagram ............................................................................................................................................................................................................ 22 Terminal strip numerical assignment .............................................................................................................................................................
ELECTRICAL CONNECTIONS Connection diagram ATTENTION! NOTE The electrical connection must only be carried out by properly qualified personnel. The instrument version can be identified by means of the type code (See nameplate on the housing).
ELECTRICAL CONNECTIONS Analog inputs Outputs Output 1 to 6 X X X X 1 analog output + - 1 logic output 0/22 V * 22 23 24 0/4 - 20 mA 0/2 - 10 V A GND 19 20 21 1 solid/state relay 230 V/1 A 16 17 18 2 logic outputs 0/5 V A1 A2 GND 13 14 15 1 changeover S P Ö 9 10 11 12 2 make K1 K2 5 6 7 8 * or supplz for 2-wire transmitter Supply voltage Interface COM.
ELECTRICAL CONNECTIONS 24 - 1150
OPERATION AND CONTROLLER FUNCTIONS OPERATION AND CONTROLLER FUNCTIONS Operation .............................................................................................................................................................................................................................................. 26 Displays and controls .......................................................................................................................................................................
OPERATION AND CONTROLLER FUNCTIONS Operation Displays and controls Front view Displays and controls (1) Status line with time, date, name of screen template and instrument name (2) Color screen (screen templates can be configured) Factory setting for fixed-setpoint controller: process value, setpoint, output (bar graph) Factory setting for program controller: process value, setpoint, program number/name, segment number, remaining programm time (3) Info/alarm symbol (4) Title Current meaning of the softkey
OPERATION AND CONTROLLER FUNCTIONS Symbols in display Symbol Meaning Info Alarm is present Automatic mode/Program is running (blue) Manual mode/"Manual" operating mode (green) Controller manual mode Self-optimization is active (symbol flashes) Ramp function is active Program pause Actuator open (modulating controller) Actuator closed (modulating controller) 1150 - 27
OPERATION AND CONTROLLER FUNCTIONS Overview of operation Screen operating loop see Chapter Configuration/Display Menu Program start menu Details Setpoint/ Manual output (> 2 s) Time Out 28 - 1150 = back to the screen operating loop = If no key is pressed the display will automatically return to the screen operating loop after a definable time.
OPERATION AND CONTROLLER FUNCTIONS Screen operating loop The operating loop contains the screen templates for a maximum of four controller channels, the collective picture of all the active controller channels, the recording function as well as two freely definable screen templates. The screen templates can be individually switched into display.
OPERATION AND CONTROLLER FUNCTIONS Menu • User level With the help of this screen template, the user can compile parameters that have to be frequently altered, through the setup program. This screen template is only displayed when appropriately configured. • Operating level Here the setpoints for all four controller channels are defined and self optimization is started (see Chapter “Self-optimization“).
OPERATION AND CONTROLLER FUNCTIONS Entering values and selecting settings Entering values Parameters can be altered in a number of screen templates: Select parameters Increase parameter value with Decrease parameter value with The longer the key is pressed the faster the value changes. Approx. 2 sec after releasing the key, the entry will be automatically accepted. Parameters can be altered within their range of values or within the maximum displayable values (e. g. two decimal places: -99.99 to +99.99).
OPERATION AND CONTROLLER FUNCTIONS Setpoint input Configuration in controller Each controller channel has four setpoints and the provisions to switch between them.
OPERATION AND CONTROLLER FUNCTIONS Recording Screen template The recording function can be used to show the traces of up to four analog signals and the switching actions of up to three logic signals.
OPERATION AND CONTROLLER FUNCTIONS Operation “Controller“ If the instrument has been configured as a fixed-setpoint controller, the following actions can be performed in automatic/manual mode: Altering the setpoint The active setpoint of a controller channel can be altered in the corresponding screen template. The controller must be in automatic mode.
OPERATION AND CONTROLLER FUNCTIONS Altering the output for modulating controllers In the case of modulating controllers, the keys are used to directly influence the right and left motion of a motorized actuator. The output is only indicated if the output feedback is connected. - open actuator - close actuator The manual mode can be inhibited.
OPERATION AND CONTROLLER FUNCTIONS Operating „program controller/generator“ If the instrument is configured as a program controller/generator, programs have to be created first, by using the internal program editor or the setup program. Program editor General 50 programs with up to 99 segments can be programmed; a total of 1000 segments can be implemented. Programs are created by programming setpoints and segment times, segment by segment.
OPERATION AND CONTROLLER FUNCTIONS Program editor edit program Call up with Select program using the cursor keys Select program channel using the cursor keys Number of program channel Program number and name Number of program segments Entry mode - edit - temporary alteration Parameter set number Lower and upper tolerance band Number of repeat cycles (Cy) with start segment (No.
OPERATION AND CONTROLLER FUNCTIONS Entering a new program The segments are edited in sequence when creating a new program. Append a new segment to the last segment of the profile trace with Copying segments Existing segments can be copied and inserted in another position in the program. The segment that was copied is inserted above the cursor position.
OPERATION AND CONTROLLER FUNCTIONS Starting the program Immediate start of program The program displayed on the screen in the basic status is started. Start program with A program can also be selected, started and canceled via the logic functions. The logic function “Program selection” has priority over the settings in the menu “Program start”. (see Chapter “Logic functions“) Selecting and starting the program The representation of the program selection can be configured as a list or an icon.
OPERATION AND CONTROLLER FUNCTIONS Overview of operation The diagram below provides an overview of the different operating modes and operating options of a program controller. Many operating options can also be implemented via the logic functions. Buttons and can be accessed via “Details”.
OPERATION AND CONTROLLER FUNCTIONS Shifting the program profile The function “External setpoint with correction” can be used to shift the program profile upwards or downwards. The external setpoint is defined via an analog signal (see Chapter “Controller”).
OPERATION AND CONTROLLER FUNCTIONS 42 - 1150
PARAMETERIZATION PARAMETERIZATION 1150 - 43
PARAMETERIZATION Parameter sets General Two parameters sets can be stored for each controller channel. Access code Factory-set code: 0001 The access code can be modified via the setup program. Parameter level / Controller 1 (2...4) / Parameter set 1 (2) Parameter Value range Factory setting Meaning Controller structure 1 P, I, PD, PI, PID PID Only PI and PID can be implemented on modulating controllers.
PARAMETERIZATION Controller structure 2 / ... Controller structure 2 P, I, PD, PI, PID PID Proportional band 0 - 9999 Digit 0 Digit Derivative time 0 - 9999 s 80 sec Reset time 0 - 9999 s 350 sec Cycle time 0 - 9999 s 20 sec Switching differential 0 - 999 Digit 1 Digit Minimum relay ON time 0 - 60 s 0 sec NOTE The parameters refer to the second controller output for 2-setpoint and modulating controllers. The parameter display on the instrument depends on the controller type selected.
PARAMETERIZATION 46 - 1150
CONFIGURATION CONFIGURATION Parameters and functions at the configuration level .................................................................................................................. 48 Analog inputs ............................................................................................................................................................................................................................... 51 Controller .............................................................
CONFIGURATION Parameters and functions at the configuration level General The following applies to the representation of parameters and functions at the configuration level: The parameter is not displayed or cannot be selected if • the instrument features do not permit the function assigned to the parameter. Example: Output 3 cannot be configured if no output 3 is available in the instrument. • the parameter is irrelevant to the function that has been configured.
CONFIGURATION Process value C4 Setpoint C4 Ramp end C4 Control dev. C4 Output C4 Y cascade C1 ... Y cascade C4 Setpoint 1 C1 ... Setpoint 4 C1 Setpoint 1 C2 ... Setpoint 4 C2 Setpoint 1 C3 ... Setpoint 4 C3 Setpoint 1 C4 ... Setpoint 4 C4 Setpoint 1 PCh1P ... Setpoint 1 PCh4P Setpoint 2 PCh1P ... Setpoint2 PCh4P Seg. end val. PCh1P ... Seg. end val. PCh4P Output 1 C1 Output 2 C1 Output 1 C2 Output 2 C2 Output 1 C3 Output 2 C3 Output 1 C4 Output 2 C4 RemSegT PCh1P ... RemSegT PCh4P Seg. Time PCh1P ... Seg.
CONFIGURATION E.G. Binary selectors Switched off Output 1 C1 Output 2 C1 Output 1 C2 Output 2 C2 Output 1 C3 Output 2 C3 Output 1 C4 Output 2 C4 Limit comp. 1 ... Limit comp. 16 Contr. contact 1P ... Contr. contact 8P Logic input 1 ... Logic input 6 Logic 1 ... Logic 8 Binary logic value Program endP Ramp end 1F ... Ramp end 4 F Tolerance bandP Manual mode C1 ...
CONFIGURATION Analog inputs Configuration Analog inputs Controller Depending on the instrument version, up to four analog inputs are available. The analog inputs are numbered in sequence (input 1 — 4) according to their slot assignment. Generator Limit comparators Outputs Logic functions Math / Logic C-level Display Interfaces Device data Recording Analog input 1 (2 to 4) / ...
CONFIGURATION Analog input 1 (2 to 4) / ... Value / selection Description Linearization Linear Pt100 Pt100 JIS Ni100 Pt500 Pt1000 Ni1000 Pt50 CU50 Pt K9 KTY11-6 Fe-CuNi J NiCr-CuNi E NiCr-Ni K NiCrSi-NiSi N Cu-CuNi T Pt30Rh-Pt6Rh B Pt13Rh-Pt R Pt10Rh-Pt S Cu-CuNi U Fe-CuNi L W5Re_W26Re C W3Re_W25Re D W3Re_W26Re C-level Customized 1 Customized 2 Customized 3 Customized 4 For customized linearizaton (e.g.
CONFIGURATION Analog input 1 (2 to 4) / ... Value / selection Description Range Start - 1999 to + 9999 The instrument will change over earlier to the response defined for overrange / underrange if the range is restricted. Example: Pt100 (Range: - 200 to + 850 °C). An alarm message is to be generated for temperatures outside the range 15 to 200 °C.
CONFIGURATION Analog input 1 (2 to 4) / ... Value / selection Description Recalibration Start - 1999 to 0 to + 9999 (See below for explanation) End - 1999 to 1 to + 9999 NOTE As opposed to all the other settings, entry of the start and end value is linked to the latest measurement at the input concerned. As a rule, these values cannot be adopted by another instrument.
CONFIGURATION Programming (1) Move to measurement point (2) Enter start value 1) (3) Move to measurement point (4) Enter end value E 1) 1) If start value=0 or end value=1 is to be set, then the value must first be altered using to enable correction. NOTE If recalibration is carried out without a reference instrument, the offset account when moving to measurement point (3). or must be taken into To cancel recalibration, the start and end values have to be programmed to the same value.
CONFIGURATION Controller Configuration Analog inputs Controller The following are set here: controller type, input variables of the controller, the setpoint limits, conditions for manual mode and the presettings for selfoptimization of the four controller channels.
CONFIGURATION Controller 1 (2 to 4) / Configuration Value / selection Description Dead band The output movement is suppressed within the dead band; e.g. with noisy signals. 0 to 100 The dead band is only effective for controller structures with an I-component.
CONFIGURATION Controller 1 (2 to 4) / Inputs Value / selection Description Process value (Analog selector) Analog inp. 1 Defines the source for the process value of the control channel. External setpoint (Analog selector) Switched off Activates the external setpoint input and defines the source for the external setpoint. Program setpoint (Analog selector) Setpt.1 PROF1 Assigns one of the four available profile traces to the controller channel. "No funct.
CONFIGURATION Controller 1 (2 to 4) / Self-optimization Value / selection Description Method Oscillation Step response One of two procedures can be selected for self-optimization. (see Chapter Optimization) Self-optimization Enabled Inhibited If the function is inhibited, self-optimization cannot be started from the keys or the logic input.. Output 1 for "Tune" Relay + logic Solid-state Analog The type of the physical output for the signal of the controller output 1 has to be defined.
CONFIGURATION Generator The basic function of the instrument is defined here. The instrument with all the available controller channels can be operated as a fixed setpoint controller, program controller or program generator. Configuration Analog inputs Controller Generator Limit comparators Outputs Furthermore, ramp functions (fixed-setpoint controller) can be activated for the individual controller channels with different parameters defined for the program controller/ generator.
CONFIGURATION Ramp / Ramp controller 1 (2 to 4) Value / selection Description FunctionF Defines whether the ramp function is to be activated for the corresponding controller channel. Inactiv Activ Unit of slopeF Defines the unit of the slope in kelvin per unit of time. K / minute K / hour K / day Ramp slopeF Amount of slope 0 to 9999 Program / ... Value / selection Description Program start P Program start at the first programmed setpoint.
CONFIGURATION Program / ... Value / selection Description Response to power failureP Prog. canceled Continue Standstill Continue X % Continue PV Response of the program run on a power failure. Program canceled: Program run canceled; instrument switches to basic status. Continue: The program continues from the point at which it was canceled at the time of the supply failure. Standstill: Outputs, limit comparators, control contacts and controller respond as was defined in the system status "Basic status".
CONFIGURATION Program / ... Value / selection Description Start at timeP No Yes Starts the program after an adjustable start delay, or at a time that can be defined (start with time delay). Setting the Clock: (see Chapter Device data) Program end timeP - 1 to 0 to 9999 s Duration of program end signal -1 = continous signal until acknowledgement (see Chapter Outputs) Function controlP (.../Controller 1 to 4, .../1 to 16. Limit comparator Generator control Control contact 1 ...
CONFIGURATION Limit comparators Configuration Analog inputs Controller Limit comparators (limit monitors, limit contacts) can be used to monitor an input variable (limit comparator process value) against a fixed limit or another variable (limit comparator setpoint). When a limit is exceeded, a signal can be output or an internal controller function initiated. Generator Limit comparators 16 limit comparators are available.
CONFIGURATION 1. (2 to 16.) Limit comparator / ... Value / selection Description LK function No function LK type 1 ... LK type 8 Limit comparator function. -1999 to 0 to +9999 Limit value to be monitored. Switching differential 0 to 1 to 100 Switching differential Xsd. Action Absolute Relative See explanation on next page. Range response Relay OFF Relay ON Function on over / underrange. Switch-on delay Delays the switch-on edge by a definable time period.
CONFIGURATION Absolute At the time of alteration, the limit comparator acts in accordance with its function. Relative The limit comparator is in the OFF status. An alteration of the limit value or the (limit comparator) setpoint could cause the limit comparator to switch ON. Such a reaction will be suppressed, and this condition is maintained until the (limit comparator) process value has moved away from the switch-on region (gray area).
CONFIGURATION Outputs Configuration of the instrument outputs are subdivided into analog outputs (max. 6) and logic outputs (max. 12). Display and numbering of the outputs depends on the assignment of the output slots Output 1- 6.
CONFIGURATION Analog outputs / Analog output 1 (2 to 6) / ... Value / selection Description Zero point - 1999 to 0 to + 9999 A physical output signal is assigned to the value range of a output variable. Example: Setpoint 1 (value range: 150 to 500°C) is to be output via the analog output (0 to 20 mA). i.e.: 150 to 500 °C = 0 to 20 mA Zero point: 150 / End value: 500 End value - 1999 to 100 to + 9999 A physical output signal is assigned to the value range of a output variable.
CONFIGURATION Logic functions Configuration Analog inputs Controller Generator Limit comparators Outputs Functions are assigned here to the logic signals of the logic inputs, limit comparators and logic functions (formula). In addition, the functions for control contacts, tolerance band signal and program end signal are defined for program controllers/generators. In the case of the fixed-setpoint controller, the ramp end signals can have functions assigned.
CONFIGURATION Combined logic functions The functions are implemented through the combination of up to four control variables. Any control variable can be selected. The states Z1 to Z4 are assigned to the control variables in descending order of the control variables (see list on the right). Example: The process value is to be selected via a logic input and the state of one limit comparator.
CONFIGURATION Program selection Program Z4 Z3 Z2 Z1 Program 1 0 0 0 0 Program 2 0 0 0 1 Program 3 0 0 1 0 Program 4 0 0 1 1 ... ... ... ... ... Program 16 1 1 1 1 0 = contakt open / OFF 1 = contakt closed / ON Multifunctional logic functions Logic functions can cover several functions simultaneously.
CONFIGURATION Selection of functions Logic input 1 (2 to 6) / ... Limit comparator (2 to 16) / ... Logic 1 (2 to 8) / ... Control contact 1 (2 to 8) / ... Tolerance band signal / ... Program end signal / ... Ramp end signal 1 (2 to 4) / ...
CONFIGURATION Logic input 1 (2 to 6) / ... Limit comparator 1 (2 to 16) / ... Logic 1 (2 to 8) / ... Control contact 1 (2 to 8) / ... Tolerance band signal / ... Program end signal / ... Ramp end signal 1 (2 to 4) / ...
CONFIGURATION Math and logic module Analog inputs Special controller types (differential, ratio, humidity, C-level controller) or mathematical formula and logic combinations are configured here. Controller C-level control and math/logic formula (math and logic module) are extras. Generator The results of the calculations can be called up, under the variables “Math X” (math formulae) and “Logic X” (logic formulae) (X=1 — 8).
CONFIGURATION Ratio control Control is always based on variable a. The math module forms the ratio of the measurements of a and b (a/b) and produces the setpoint for the controller. The ratio is made available as a value, via the function “Math X”, and can be displayed. The required ratio a/b is programmed as the setpoint (ratio setpoint) in the setpoint definition.
CONFIGURATION C-level control Configuration Analog inputs Controller Generator C-level control is used for the control of carbon in the atmosphere of a gas coking furnace. The C-level is determined through the oxygen measurement with a zircon dioxide sensor and measurement of the sensor temperature. C-level control is an extra.
CONFIGURATION Value / selection Description Sensor voltage (Analog selector) Switched off Source for the voltage signal of the zircon dioxide sensor.
CONFIGURATION Display Configuration Analog inputs Controller Generator The time-dependent screen saving is defined here. In addition, time-out and the sequence of the different screen templates can be defined. The representations on the controller pictures 1 - 4 and on the collective picture can be adapted to suit individual requirements.
CONFIGURATION Value / selection Description Operation loop ... / Controller pic. 1 ... / Controller pic. 2 ... / Controller pic. 3 ... / Controller pic. 4 ... / Collective pic. ... / Recording ... / Custom pic. 1 ... / Custom pic. 2 The screen templates that are to appear in the screen operating loop can be selected. Yes No Controller pictures / Controller picture 1 (2 to 4) / ... Value / selection Description Analog value 1 Display for fixed-setpoint controller: ...
CONFIGURATION Collective picture / Controller 1(2 to 4) / ... Value / selection Description Value column 1 Display: (Analog selector) Ramp end C1 Decimal point column 1 XXX.X Controller Controller Controller Controller 1 2 3 4 Value column 2 (Analog selector) Setpoint C1 Column 1 Column 2 Column 3 Decimal point column 2 XXX.
CONFIGURATION Interfaces Configuration Analog inputs Controller The interface parameters for the standard RS422/485 interface (MODbus 1) and an optional RS422/485 (MODbus 2) or Profibus-DP interface have to be configured in order to communicate with PCs, bus systems and peripheral devices. Generator Limit comparators Outputs Logic functions Math / logic C-level Display Interfaces Device data Recording MODbus / ... Value / selection Description Protocol MODBUS MODBUS int.
CONFIGURATION Device data Configuration Basic settings such as supply frequency or temperature unit are made here. Analog inputs Controller Generator Limit comparators Outputs Logic functions Math / logic C-level Display Interfaces Device data Recording Value / selection Description Device designation (16-character text) any text Supply frequency 50 Hz 60 Hz Country-specific supply frequency of supply voltage.
CONFIGURATION Recording Configuration Analog inputs The recording function permits the visualization of up to four analog and three logic signals. The signal sources are defined here. Controller Generator Limit comparators Outputs Logic functions Math / logic C-level Display Interfaces Device data Recording Analog value 1 (2 to 4) / ... Value / selection Description Function (Analog selector) Switched off Recording of analog signals Scaling start Defines the lower and upper limit on the y-axis.
CONFIGURATION 84 - 1150
OPTIMIZATION OPTIMIZATION Self-optimization ....................................................................................................................................................................................................................... 86 Oscillation method ..................................................................................................................................................................................................................
OPTIMIZATION Self-optimization Oscillation method Self-optimization SO establishes the optimum controller parameters for PID or PI controllers.
OPTIMIZATION NOTE With output type “solid-state”, the cycle time during optimization is reduced to 8 x the sampling time. With the “relay” output type, care has to be taken that the process value is not influenced by the switching cycle time, otherwise optimization cannot be completed successfully. Solution: Reduce the cycle time Cy, until the process value is no longer influenced.
OPTIMIZATION Starting self-optimization Start at the operating level Select the controller channel in / Operation level / Self-optimization / Controller number 1 to 4 Start self-optimization for the selected controller channel with / Status / „Active“ Start from the operating loop Change the screen template for the required controller channel with necessary!) (press repeatedly, if Press Press Start self-optimization for the required controller channel with Pressing NOTE resets the significance of the
OPTIMIZATION Check of the optimization The optimum adaptation of the controller to the process can be checked by recording the start-up phase with the control loop closed. The diagrams below indicate possible adjustment errors and how these can be corrected. The control response of a third-order control loop of a PID controller is shown as an example. However, the procedure for adjusting the controller parameters can also be applied to other control loops.
OPTIMIZATION 90 - 1150
RETROFITTING OF MODULES RETROFITTING OF MODULES Safety notes .................................................................................................................................................................................................................................. 92 Identifying the module .....................................................................................................................................................................................................
RETROFITTING OF MODULES The following steps are necessary for retrofitting modules: Safety notes ATTENTION! Only qualified personnel are permitted to install retrofit modules. ATTENTION! The modules can be damaged by electrostatic discharge. Avoid electrostatic charge during installation and removal. Carry out retrofitting on a workbench that is properly grounded and follow ESD precautionary measures. Identifying the module Identify the module by the Sales. No.
RETROFITTING OF MODULES Removing the back panel from the housing Pull off the pluggable connector Loosen screws (do not remove (1) and (2)!) Fold back panel upwards and take it off 1150 - 93
RETROFITTING OF MODULES Slot assignment The slots for the individual modules are printed on the back panel of the housing: Slot Module Function Input 1 ... Input 4 Universal input Analog input 1 ... Analog input 4 Output 1 ... Output 6 Outputs Output 1+71 ... Output 6+121 Com 2 RS422/485 PROFIBUS-DP Ethernet Interface 2 1 Number of output, if two outputs are available on the board. Retrofitting of modules Remove dummy module or existing module by using a screwdriver or similar tool.
RETROFITTING OF MODULES Push module into the vacant slot until the pluggable connector snaps into place Hook the back panel into the slots provided on the top edge and close it.
Contact addresses / Kontaktadressen Germany / Deutschland / Allemange Bürkert Fluid Control System Sales Centre Chr.-Bürkert-Str. 13-17 D-74653 Ingelfingen Tel. + 49 (0) 7940 - 10 91 111 Fax + 49 (0) 7940 - 10 91 448 E-mail: info@de.buerkert.com International Contact addresses can be found on the internet at: Die Kontaktadressen finden Sie im Internet unter: Les adresses se trouvent sur internet sous : www.burkert.
The smart choice of Fluid Control Systems www.buerkert.