SYSTEM DESCRIPTION
Measurement circuit monitoring
In the event of fault, the outputs move to a defined (configurable) status.
Sensor Overrange /
underrange
Probe or lead short-circuit Probe or lead break
Thermocouple
-
Resistance thermometer
Voltage 2 to 10V
 0 to 10V
-
-
Current 4 to 20 mA
 0 to 20 mA
-
-
 
recognized  - not recognized
Logic inputs
Input for standard signals
Floating contacts
Designation Measurement range Meas. accuracy
1
Ambient
temperature
error
Voltage  0 to 10 V
 -10 to +10 V
 -1 to +1 V
 0 to +1 V
 0 to 100 mV
-100 to +100 mV
Input resitance R
E
   100 k 
 0.05 %
 0.05 %
 0.05 %
 0.05 %
 0.05 %
 0,05 %
100 ppm/K
100 ppm/K
100 ppm/K
100 ppm/K
100 ppm/K
100 ppm/K
Current 4 to 20 mA, voltage drop    1 V
0 to 20 mA, voltage drop  1 V
 0.1 %
 0.1 %
100 ppm/K
100 ppm/K
Heater current 0 to 50 mA AC
 1 %
100 ppm/K
Potentiometer min. 100    max. 10 k 
1
 With 250 msec sampling time.
Outputs
Relay
 contact rating
 contact life
changeover contact or 2 x make
3A at 250 V AC resistive load
150.000 operations at rated load
Logic
 current limiting
0/5 V
20 mA
or 0/22 V
30 mA
Solid-state relay
 contact rating
 protection circuitry
1 A at 230 V
varistor
Voltage
 output signals
 load resistance
0 to 10 V / 2 to 10 V
R
Last
  500  
Current
 output signals
 load resistance
0 to 20 mA / 4 to 20 mA
R
Last
    450  
Supply voltage for 2-wire
transmitter
 voltage
 current
22 V
30 mA