User guide

52 - 1150
CONFIGURATION
Analog input 1 (2 to 4) / ...
The controller uses the corrected value (l.e. displayed value) for its computation. This value
does not correspond to the actual measured value.
If incorrectly applied, this can result in impermissible values of the control variable.
Value / selection Description
Linearization
Linear
Pt100
Pt100 JIS
Ni100
Pt500
Pt1000
Ni1000
Pt50
CU50
Pt K9
KTY11-6
Fe-CuNi J
NiCr-CuNi E
NiCr-Ni K
NiCrSi-NiSi N
Cu-CuNi T
Pt30Rh-Pt6Rh B
Pt13Rh-Pt R
Pt10Rh-Pt S
Cu-CuNi U
Fe-CuNi L
W5Re_W26Re C
W3Re_W25Re D
W3Re_W26Re
C-level
Customized 1
Customized 2
Customized 3
Customized 4
For customized linearizaton (e.g. „customized 1“) a maximum of 20 knee-points can
be implemented, or a 5th order polynominal function programmed (only with setup
program).
„C-level“ linearization is used for the C-level control with a zircon dioxide sensor.
For the linearization „KTY11-6“, the resistance is 2 k at 25 °C. The resistance
value can be adapted via the parameter „KTY: at 25°C / 77°F.
Offset
- 1999 to 0 to + 9999 The offset is used to correct a measured value by certain amount upwards or
downwards.
Example:
Measured Displayed
value Offset value
294,7 + 0,3 295,0
295,3 - 0,3 295,0
NOTE