Manual

24
Installation and wiring
Type 8011
With regulating valve
Pipe with 2 elbows at 90°
in 3 dimensions
Pipe with 2 elbows
at 90°
Pipe with 1 elbow at 90° or 1
T-piece
With pipe expansion With pipe reduction
50 x DN
5 x DN
40 x DN
5 x DN
25 x DN
5 x DN
20 x DN
5 x DN
18 x DN
5 x DN
15 x DN
5 x DN
Fig. 4: Upstream and downstream distances depending on the
design of the pipes.
If necessary, use a flow conditioner to improve measurement
precision.
Install the device in such a way that the paddle-wheel axis is
horizontal.
On an horizontal pipe, mount the device in such a way that the
paddle-wheel is downwards (Fig. 5).
Prevent the formation of air bubbles in the pipe in the section
around the device (Fig. 6).
Ensure that the pipe is always filled in the section around the
device (Fig. 7).
Fig. 5: Paddle-wheel downwards on an horizontal pipe
Correct
Correct
Incorrect
Incorrect
Fluid circulation
direction
Fig. 6: Air bubbles within the pipe
Correct
Incorrect
English