Manual
25
Installation and wiring
Type 8011
Correct
Incorrect
Fig. 7: Filling the pipe
7.2.2. Installing a device with welding
ends
note
The SE11 electronic module and the seal may be damaged
when welding the connections to the pipe.
• Before welding to the pipe, unscrew the 4 locking screws on
the SE11 electronic module.
• Remove the electronic module.
• Remove the seal.
→ Follow the installation recommendations in chap. 7.2.2.
→ Weld the connections.
→ After welding the connections to the pipe, correctly replace the
seal.
→ Properly replace the electronic module.
→ Tighten the 4 screws in an alternating pattern, applying a torque
of 1.5 Nm.
7.2.3. Installing a device with Clamp
connections
→ Follow the installation recommendations in chap. 7.2.1.
• Check that the seals are in good condition.
• Place the seals, that have been chosen depending on the
process temperature and fluid, into the grooves of the
Clamp connections.
→ Fit the Clamp connections to the pipe using a clamping collar.
7.2.4. Installing a device with flange
connections
→ Follow the installation recommendations in chap. 7.2.1.
• Check that the seals are in good condition.
• Insert a seal, that has been chosen depending on the
process temperature and fluid, into the grooves of the
connections.
Make sure the seal remains in its groove when tightening
the flange.
→ Tighten the flange to mount the device to the pipe.