Manual

27
Installation and wiring
Type 8011
7.4. Electrical wiring
danger
Risk of injury due to electrical discharge
Shut down and isolate the electrical power source before carry-
ing out work on the system.
Observe all applicable accident protection and safety regula-
tions for electrical equipment.
note
Use cables with an operating temperature limit suitable for your
application.
Protect the power supply of a version with 2 pulse outputs by
means of an 800 mA fuse and a switch.
Protect the power supply of a version with 1 pulse output by
means of a 50 mA fuse and a switch.
Use a high quality electrical power supply (filtered and
regulated).
Under normal conditions of use, cable with a cross section
of 0.75 mm
2
should be enough to transmit the signal.
Do not install the cable near high voltage or high frequency
cables.
If this is unavoidable, keep a minimum distance of 30 cm.
Make sure the installation is equipotential (power supply
- 8011):
Connect the different earth connections of the installation to
one another in order to remove any differences in potential
which may arise between two earth connections.
Correctly connect the cable shielding to the earth.
Connect the negative power supply terminal to the earth to
eradicate the effects of common mode currents. If this con-
nection cannot be made directly, a 100 nF/50 V capacitor
can be fitted between the negative power supply terminal
and the earth.
+
-
(*)
(**)
Power supply
8011 with cable gland
+
-
(*)
(**)
Power supply
8011 with M12 fixed
connector
*) If a direct earth connection is not possible, fit a 100 nF/50 V condenser
between the negative power supply terminal and the earth
**) If the cable used is shielded.
English