Owner manual

31
Installation and wiring
Type 8012
7.4. Electrical wiring
danger
Risk of injury due to electrical discharge
Shut down and isolate the electrical power source before
carrying out work on the system.
Observe all applicable accident protection and safety regula-
tions for electrical equipment.
note
Use cables with an operating temperature limit suitable for your
application.
Use a high quality electrical power supply (filtered and
regulated).
of 0.75 mm
2
should be enough to transmit the signal.
cables.
If this is unavoidable, keep a minimum distance of 30 cm.
Make sure the installation is equipotential (power supply
- 8012):
Connect the different earth connections of the installation to
one another in order to remove any differences in potential
which may arise between two earth connections.
Correctly connect the cable shielding to the earth.
Connect the negative power supply terminal to the earth
to eradicate the effects of common mode currents. If this
connection cannot be made directly, a 100 nF/50 V capacitor
can be fitted between the negative power supply terminal
and the earth.
Power supply
+
-
(*)
12-36VDC
8012 with cable gland
+
-
(*)
12-36VDC
(**)
Power supply
8012 with M12 fixed
connector
*) If a direct earth connection is not possible, fit a 100 nF/50 V condenser
between the negative power supply terminal and the earth
**) If the cable used is shielded.
English