Owner manual
33
Installation and wiring
Type 8012
12-36 VDC
+-
(*)
1 2
34
5
blue
grey
whitebrown
Power supply
Load
Fig. 11 : PNP wiring of the pulse output of a version with M12 fixed
connector
12-36 VDC
+-
+-
(*)
1 2
34
5
Power supply
brown
blue
black
grey
4-20mA
input at
external
device
Fig. 12 : Wiring the current output in sinking mode (by default) on a
version with M12 fixed connector.
12-36 VDC
+-
+-
(*)
1 2
34
5
Power supply
black
blue
grey
brown
4-20mA
input at
external
device
Fig. 13 : Wiring the current output in sourcing mode on a version
with M12 fixed connector
(*) Functional earth; If a direct earth connection is not possible, fit a 100 nF /
50 V capacitor between the negative power supply terminal and the earth.
7.4.3. Wiring a version with cable gland
Color of the
wire
BN (brown)
WH
(white)
GN (green) YE (yellow)
GY
(grey)
Signal on a
version with
pulse output
V+ (12-36 V DC) 0 V DC
Functional
earth
Not connected
NPN or
PNP
Signal on a
version with
pulse and
current outputs
V+ (12-36 V DC) 0 V DC
Functional
earth
Current in mA
NPN or
PNP
English