the K-factor of the
measuring device or have it
calculated through the Teach-
in feature**�
K is the multiplication coeffi-
cient between the frequency
transmitted by the remote
sensor and the flow rate to be
measured�
the flow rate unit
(l/s, l/min, l/h, m
3
/min, m
3
/h,
Ga/s, Ga/min, Ga/h)�
to the previous
feature�
the next function�
UNIT
l/s
GA/H
KFAC
NO
TEAC
YES
TEAC
TEAC
0.534
KFAC
200.0
VOL
0.534
KFAC
** To use the «Teach-In» feature, connect the 8032 controller to a valve which makes it possible to fill a tank with a capacity of
x litres (200 litres for instance)�
When the display shows «YES TEAC», press the «ENTER» key and open the valve: The «TEAC» message flashes�
When the tank is full (200 litres), press «ENTER» again� By means of keys
0......9
and
ENTER
enter the volume of fluid which
circulated through the circuit (200 litres): the controller calculates the K factor and displays it�
**
* To move the decimal point, press simultaneously keys
0......9
and