User Manual

12
Technical data
Type 8025/8035 /
Pulse output
type
function
frequency (f)
electrical data
duty cycle
protection
polarized, potential-free
NPN/PNP (wiring dependant)
pulse output, adjustable pulse
value
2,5-400 Hz
5-36 V DC, 100 mA max.,
voltage drop 2,5 V DC at
100 mA
0,5
galvanically isolated, and
protected against over-
voltages, polarity reversals
and short-circuits
Relay outputs
operating
electrical data of the load (non
UL recognized devices)
electrical data of the load (UL
recognized devices)
hysteresis, adjustable
thresholds, normally open
230 V AC / 3 A
30 V AC max. and 42 V peak
or 60 V DC max.
Current output
response time (10% to 90%)
max. loop impedance,
12-36 V DC version
max. loop impedance,
115/230 V AC version
wiring, version without relays
wiring, version with relays
4-20 mA, sinking or sourcing
mode (through wiring)
5,75 s (default)
900W at 30 V DC, 600W at
24 V DC, 50 W at 12 V DC
800 W
2-wire
3-wire
Protection against polarity
reversals
yes
6.6. Specifications of the connected
flow sensor
Sensor input
signal frequency
pulse signal (Hall)
sinus signal (coil)
2,5 to 400 Hz
NPN, open collector
typical sensitivity of 35 mV peak-
peak, at 252 Hz
Sensor output
power supply 10-34 V DC (V+ subtract 2
V DC), 1 mA max.
English