Installation
Type 8025/8035 /
Install the device on the pipe in such a way that the upstream and
downstream distances are respected according to the design of
the pipes, refer to standard EN ISO 5167-1 and "Fig. 4":
flow direction
50 x DN 5 x DN
40 x DN 5 x DN
25 x DN 5 x DN 20 x DN 5 x DN
18 x DN 5 x DN 15 x DN 5 x DN
With control valve Pipe with 2 elbows at 90° in 3
dimensions
Pipe with 2 elbows at 90° Pipe with 1 elbow at 90° or 1
T-piece
With pipe expansion With pipe reduction
Fig. 4: Upstream and downstream distances depending on the
design of the pipes
Ensure that the pipe is always filled in the section around the
device (see "Fig. 5").
When mounting vertically ensure that the flow direction is in an
upward direction (see "Fig. 5").
Horizontal mounting
Correct Incorrect
Vertical mounting
Correct Incorrect
flow direction
Fig. 5: Filling of the pipe
Prevent the formation of air bubbles in the pipe in the section
around the device (see "Fig. 6").