User Manual

41
Wiring
Type 8025/8035 /
8.6.2. Wiring the 8025, remote version, 12-36 V DC, with relays
For a wall-mounted version, obey the wiring instructions of chap. "8.7.1".
Before wiring the device, configure the selectors on the electronic board (see chap. "8.3").
Connect the flow sensor to the transmitter according to chap. "8.5".
Supply
12..36Vdc
FLOW SENSOR
COILNPN
L+
L-
PE
P-
P+
NC
L+
L-
PE
P-
P+
Iout
PULSE
OUTPUT
Without
With
Relays
NPN SENSOR
1 PULSE INPUT
2 -
3 +
4 NC
SUPPLY
1234PE
REL1
REL2
COIL SENSOR
1
2
3 NC
4 NC
4
6
3
5
A
21
B
PE
Switch
A
: see chap. "8.3.1"
Switch
B
: see chap. "8.3.2"
Terminal block 1
Iout: 4-20 mA output
L+: positive power supply
L-: negative power supply
PE: wiring of the PE between the main board and the protection
board
P-: negative pulse output
P+: positive pulse output
Terminal block 2 PE
Wiring of the cable shields
Terminal block 3: wiring of relay 1, see chap. "8.4.2"
Terminal block 4: wiring of relay 2, see chap. "8.4.2"
Connector 5: connection of the flow sensor see chap. "8.5"
Jumper wire 6: jumper wire to be removed if the 4-20 mA output is
connected
Fig. 38: Terminal assignment of a panel-mounted or wall-mounted version, 12-36 V DC, with relays
English