User Manual

9
Technical data
Type 8025/8035 /
Fluid pressure (compact ver-
sions)
8025 compact
8035 with S030 fitting in
plastic
8035 with S030 fitting in metal
The fluid pressure may be
restricted by the fluid tem-
perature, the material the flow
sensor is made of (only for the
compact 8025) and the material
the fitting used is made of. See
"Fig. 2" and "Fig. 3".
PN10
PN10
PN16 (PN40 on request)
Flow rate measurement
Measurement range
- Sensor with pulse output
(Hall)
- Sensor with a sinus output
(coil)
Accuracy
- with a teach-in procedure
- with the K factor of the
fitting used
Linearity
1)
Repeatability
1)
- 0.3 m/s to 10 m/s
- 0.5 m/s to 10 m/s
- 1 % of the measured value
(at the value of the teach-in
flow rate)
- 2,5 % of the measured
value
±0,5 % of the full scale
±0,4 % of the measured value
1)
Determined in the following reference conditions: medium = water, water
and ambient temperatures 20 °C, min. upstream and downstream distances
respected, appropriate pipe dimensions
10
9
8
7
6
5
4
3
2
1
0
-15 0 +20 +40 +60
PVDF
PVDF (PN10)
PVC (PN10)
PP (PN10)
PVC + PP
11
P (bar)
T (°C)
+80
A
Metal
A: range of use
Fig. 2: Fluid temperature /pressure dependency curves for the
8025 compact version, depending on the material the
S020 fitting is made of
English