Installation and wiring
Type 8025 /8035 Batch
7.4 Installation of a wall-mounted
version
note
Risk of material damage if the cable glands are not tightly
screwed on the housing
▶▶ Before▶installing▶the▶wall-mounted▶housing▶on▶its▶support,▶
tighten▶the▶nuts▶of▶the▶entry▶item▶of▶the▶cables▶glands▶at▶a▶torque▶
of▶1.5▶Nm.
The▶device▶in▶a▶wall-mounted▶version▶has▶4▶holes▶in▶the▶bottom▶of▶
the▶housing.
▶→ Remove▶the▶blanking▶strips▶covering▶the▶screws.
Blanking▶strips
ENTER
0....9
FLOW
Nut▶of▶the▶entry▶item
▶→ Loosen▶the▶4▶screws▶and▶open▶the▶cover▶to▶get▶access▶to▶the▶
holes▶[1].
1 1
11
106 mm
230V
LN
230V
T 250 mA
56789 10
LN
230V
CURRENT
SOURCE SINK
BINARY
PE PEPE
PE
DI1
DI2
DI3
DI4
DO4
ISOG
FLOW
SENSOR
L+ L- PE P- P+
NC
Iout
PULSE
DO1
Supply
12..36Vdc
Univ
Batch
(AO1)
SUPPLY
NC
COIL
PULSE
INPUT
NPN/PNP
213PE
+-
SENSOR
SUPPLY
LOAD
+5V
L+
(L+)-12V
COIL/PNP
39K
470
2.2K
SENSOR TYPE
COIL NPN/PNP
DO2
DO3
OFFON
106 mm
Fig. 12: Installation of a wall-mounted version
▶→ Secure▶the▶housing▶to▶the▶support▶respecting▶the▶dimensions▶
indicated▶in▶„Fig.▶12“.
▶→ Wire▶acc.▶to▶instructions▶in▶chap.▶„7.6“.
▶→ Close▶the▶housing▶and▶tighten▶the▶4▶screws▶of▶the▶cover.
7.5 Installation of a 8035 Batch
7.5.1 Recommandations for installing the
8035 Batch on the pipe
The▶electronic▶module▶SE35▶Batch▶can▶be▶installed▶on▶a▶pipe▶by▶
using▶a▶sensor-fitting▶S030.
▶→ Choose▶an▶S030▶fitting▶appropriate▶to▶the▶velocity▶of▶the▶fluid▶
inside▶the▶pipe.
English