User Manual

28
Installation and wiring
1
2
3
Respect the installation instructions given in the operating instructions
of the fitting.
Insert the electronic module SE35 [2] in the sensor-fitting S030 [1].
Secure the electronic module to the sensor-fitting by a 30° turn.
Secure the unit by tightening screw [3].
Figure 15: Installation of a 8035 Batch
7.6 Wiring
danger
Risk of injury due to electrical voltage.
Shut down the electrical power source of all the conductors and isolate it before carrying out work on the
system.
Observe all applicable accident protection and safety regulations for electrical equipment.
Insert the supplied stopper gaskets into the unused cable glands of a compact or wall-mounted version to
ensure the tightness of the device.
Only move the selectors when the power supply is off.
Use a filtered and regulated 12-36 V DC power supply.
• Make sure the installation is equipotential. See chap. “7.6.1”.
• Use shielded cables with a temperature limit of 80 °C minimum.
Do not install the cables near high voltage or high frequency cables; If this cannot be avoided, observe a
min. distance of 30 cm.
Protect the device power supply by means of a 300 mA fuse and a switch.
Protect the power supply of each transistor output by means of a 125 mA fuse.
Protect the relays by means of a max. 3 A fuse and a circuit breaker (depending on the process).
Do not apply both a dangerous voltage and a safety extra-low voltage to the relays.