User Manual

55
Operating and functions
9.6.1 Doing a dosing in dosing mode "LOC. MANU." or
"MEM.+MANU."
Dosing mode "LOC. MANU." allows for entering a dosing quantity and starting the dosing, via the navigation keys.
Dosing mode "MEM.+MANU." allows for:
• either entering a dosing quantity and starting the dosing, via the navigation keys,
• or starting the dosing, via the navigation keys, of a quantity saved in the memory.
danger
Danger due to electrical voltage.
Shut down the electrical power source of all the conductors and isolate it before carrying out work on the
system.
Observe all applicable accident protection and safety regulations for electrical equipment.
Connect the valves to the DO2 and DO3 outputs: see chap. “7.6.12”.
Wire the output DO4 as described in “Figure 36”.
CURRENT
SOURCESINK
BINARY
PE PEPE
PE
DI1
DI2
DI3
DI4
DO4
ISOG
FLOW
SENSOR
L+ L- PE P- P+
NC
Iout
PULSE
DO1
Supply
12..36Vdc
Univ
Batch
(AO1)
SUPPLY
NC
COIL
PULSE
INPUT
NPN/PNP
213PE
+-
SENSOR
SUPPLY
LOAD
+5V
L+
(L+)-12V
COIL/PNP
39K
470
2.2K
SENSOR TYPE
COIL NPN/PNP
DO2
DO3
OFFON
+
-
5-36 V DC
125 mA
LED
1)
signalling the dosing state for example if the output DO4 has been
configured to transmit the state of the device.
PLC
Terminal A
2)
1)
The LED can be replaced by another indicating system depending on the configuration of the transistor output DO4. See
chap. “9.7.18”.
2)
On a version energized with a 12-36 V DC voltage, the power supply of the device can be used to energize the transistor
output DO4; If this is the case, connect the terminal "ISOG" to the terminal (L-) of terminal block A and use a 300 mA-fuse
(instead of a 125 mA-fuse) to protect the power supply.
Figure 36: Electrical connection of the transistor output DO4 in the dosing modes "LOC. MANU", "LOC. MEM",
"MEM+MANU" or "LOC. REP"
Start the device again.
Configure the device with the dosing mode "LOC. MANU." or "MEM.+MANU.": see chap. “9.7.6” or “9.7.8”.
Do a dosing as shown in “Figure 37”.
English
Type 8025 - 8035 BATCH