User Manual

61
Operating and functions
Process level (the digital inputs DI1, DI2 and DI3 are deactivated).
To choose the dosing quantity from the memory, activate the digital inputs DI1,
DI2, DI3:
State of input DI3 0 0 0 1 1 1 1
State of input DI2 0 1 1 0 0 1 1
State of input DI1 1 0 1 0 1 0 1
Associated quantity V1 V2 V3 V4 V5 V6 V7
To go back to the Process level, deactivate the 3 digital inputs DI1 to DI3.
The display alternately shows the called memory and the dosing quantity.
To start the dosing, send a pulse on the digital input DI4.
V1 00120 L
The dosing quantity is counted down (the dosing units blink).
To read the flow rate measured in the pipe, press or
0......9
.
To read the total dosing quantity, press or
0......9
once.
To interrupt the dosing, see “Figure 43”.
00117 L
1156 L
When the dosing is finished, the device is ready for a new dosing.
V1
Figure 42: Doing a dosing of a quantity from the memory, in dosing mode "EXT. MEM."
English
Type 8025 - 8035 BATCH