Technical data
Current output
Type of output
Accuracy
Refresh time
Max. loop impedance
4-20 mA, sinking or sourcing wiring
± 1% (0,16 mA)
100 ms
1100 W at 36 V DC, 330 W at
18 V DC
Frequency output
Frequency
Duty cycle
Max current
Protected against
short-circuits and
polarity reversal
0-240 Hz
50 % ± 1 %
100 mA max.
yes
Relay output Normally open or normally closed,
depending on the wiring
3 A, 250 V AC max.
Alarm
Full scale exceeded
Error signal
22 mA and 256 Hz
22 mA and 0 Hz
6.6. Electrical connections
Type of connection Through two M20x1,5 cable
glands
Cable specifications
cable type
Cross section
Diameter of each cable:
- if only one cable is used
per cable gland
- if two cables are used per
cable gland
shielded
0,5 to 1,5 mm
2
- 6...12 mm
- 4 mm, with the supplied
multi-way seal
6.7. K factors
The S020 fitting with weld end connections is available
in two versions: a version for the measuring devices with
a G2'' nut and a version for the measuring devices with a
clamp connection.
Use the K factor of the fitting used.
The device measures the flow velocity (in m/s) of the fluid and converts
it into a current (in mA) and a frequency rating (in Hz).
The current I or the frequency f are proportional to the flow rate Q (l/s),
the proportionality factor is called the "K factor":
f = K
1
*Q
I = K
2
*Q + 4
with K
1
and K
2
in pulse/litre
English