Adjustment and commissioning
Filter Position of switch 3
slow
(Response time 10 to 90 % = 14 s)
OFF
fast
(Response time 10 to 90 % = 5 s)
ON
9.6. Selecting the measurement
range
The output signal is proportional to the measured flow velocity.
Switches 4 and 5 are used to adjust the measuring range of the
device to your application.
Position switches 4 and 5 to select the measuring range (see
Fig. 26, and the following table).
After the measuring range has been modified, the per-
centages set for the low and high switching thresholds are
applied to the new full scale selected.
Measuring range Position of
switch 4
Position of switch
5
0 to 2 m/s ON OFF
0 to 5 m/s OFF ON
0 to 10 m/s OFF OFF
0 to calibrated full scale
(between 2 and 10 m/s)
ON ON
9.7. Calibrating the flow zero point
Calibrate the device on commissioning and after each
maintenance task.
Before calibrating the zero point on commissioning:
immerse the measuring element in the fluid for 24 h
before calibration.
Before calibrating the zero point after each maintenance
task:
immerse the measuring element in the fluid for 1 h before
calibration.
Before calibration, ensure that the pipe does not contain
any air bubbles and that the fluid is not moving.
Fill the pipe with fluid.
Stop the flow.
Calibrate the "zero flow" point (see Fig. 28 and Fig. 29).