User Manual
19
Setting and Functions
9.4.3. Out (Output) – Setting the output signal
In this parameter, define whether the device is to work as a flow transmitter or a pulse divider.
Setting as flow transmitter (4 - 20 mA):
When changing the unit (e.g. from liters to gallons) the limit values for the current output are not converted
automatically
→ Set the lower and upper limit values for the flow rate range associated to the 4-20 mA output, in the unit set within the
UNIT parameter.
The lower limit value is marked by an L (low) on the display and the upper limit value by an H (high).
Setting as pulse divider (PULS):
→ Set the volume, in the displayed unit, for each pulse emitted on the NPN and PNP outputs.
Setting in the parameter:
* Order of value input:
1. Select the decimal point place
(each time the key is pressed: one position to
the left)
2. Set numerical values
Status display changes to "active"
Set the flow rate range *
Set the volume pro pulse, in the displayed unit *
Lower limit value Upper limit value
Select
flow
transmitter
Select
pulse divider
mA
L
L = low H = high
Fig. 13: Out – Setting the output; operation as flow transmitter or pulse divider
English
Type 8022