Setting and Functions
9.4.3. Out (Output) – Setting the output signal
In this parameter, define whether the device is to work as a flow transmitter or a pulse divider.
Setting as flow transmitter (4 - 20 mA):
When changing the unit (e.g. from liters to gallons) the limit values for the current output are not converted
automatically
Set the lower and upper limit values for the flow rate range associated to the 4-20 mA output, in the unit set within the
UNIT parameter.
The lower limit value is marked by an L (low) on the display and the upper limit value by an H (high).
Setting as pulse divider (PULS):
Set the volume, in the displayed unit, for each pulse emitted on the NPN and PNP outputs.
Setting in the parameter:
* Order of value input:
1. Select the decimal point place
(each time the key is pressed: one position to
the left)
2. Set numerical values
Status display changes to "active"
Set the flow rate range *
Set the volume pro pulse, in the displayed unit *
Lower limit value Upper limit value
Select
flow
transmitter
Select
pulse divider
mA
L
L = low H = high
Fig. 13: Out – Setting the output; operation as flow transmitter or pulse divider
English