Installation and Wiring
Type 8071
7. INSTALLATION AND WIRING
7.1. Safety instructions
danger
Risk of injury due to high pressure in the installation.
Stop the circulation of fluid, cut off the pressure and drain the
pipe before loosening the process connections.
Risk of injury due to electrical voltage.
Shut down and isolate the electrical power source before
carrying out work on the system.
Observe all applicable accident protection and safety regula-
tions for electrical equipment.
Risk of injury due to the nature of the fluid.
Respect the prevailing regulations on accident prevention and
safety relating to the use of aggressive fluids.
Risk of injury due to high fluid temperatures.
Use safety gloves to handle the device.
Stop the circulation of fluid and drain the pipe before loosening
the process connections.
Keep all easily flammable material and fluid away from the
device.
6.4. K factors (in pulse/l)
Flow rate range K factor (in pulse/l)
0,5- 50 l/h 1552
2- 100 l/h 1000
15- 500 l/h 400
If the device is combined with an instrument which does not
automatically convert the K factors, make the conversion
using one of the following formulae:
K factor in pulse/gallon US = K factor in pulse/l x 3,785 to
obtain flow rate in gallon US / time unit
K factor in pulse/gallon UK = K factor in pulse/l x 4,546 to
obtain flow rate in gallon UK / time unit.