Owner's manual
18
Installation and wiring
4 3 2 1
→ Unscrew the nut [1] on the body [4].
→ Insert the cable into the nut [1], the cable
clamp [2] and the seal [3], and then into
the body [4].
5,5
11,5
20
5
→ Strip 20 mm of the cable.
→ Cut the central wire (earth) so that its
length is equal to 11.5 mm.
→ Expose 5.5 mm of the wires on the
stripped cable.
→ Insert each wire into the appropriate pin
on the terminal block [5] (see chap. 7.3.3
to 7.3.7).
→ Screw the terminal block [5] once wired
to the body [4]
→ Tighten the connector nut [1].
Fig. 11: Assembling an M12 female connector (not supplied )
7.3.2. Wiring a version with transistor
output and EN175301-803 male fixed
connector
DANGER
Risk of injury due to electrical voltage
• Always plug in and tighten the connectors correctly.
The device is not tight when the EN 175301-803 fixed
connector is not wired:
→ Unscrew the nut [1] (see Fig. 10) on the 2508 female
connector supplied with the device.
→ Insert the plug with order code 444509, supplied with
the device, into the cable gland.
→ Screw the nut again.
→ Plug the sealed 2508 connector onto the
EN 175301-803 fixed connector.
1
2
3
1
2
3
1: V+ (12-36 V DC)
2: Transistor output (NPN or PNP)
3: 0 V DC
4: Functional earth
Fig. 12: Pin assignment of the EN175301-803 fixed connector
English
Installation and wiring