Adjustment and functions
9.5.4. Setting the flow rate range
associated to the 4-20 mA output
The 4-20 mA output provides an electrical current, the value of
which reflects the flow rate measured by the device.
The signal may be inverted, i.e. the flow rate value associated to the
20-mA current is lower than the one associated to the 4-mA current.
The current output gives a 22-mA current when the device shows
an operating error.
4
20
20 180
mA
l/min
Fig. 38: Example of relation between the measuring range and
the current output
ENTER
0......9
*
0......9
*
ENTER
ENTER
MA
0.200
4ma
1.000
20ma
To function "FILT"
* to move the
decimal point,
simultaneously
press keys
0......9
and
Enter the flow rate values, in the unit that has been chosen in the
UNIT parameter, related to the 4-20-mA current range.
9.5.5. Choosing the filter of the flow rate
To function "BRGR"
ENTER
0......9
ENTER
FILT
2
FILT
The "Filter" function is used to attenuate the display and 4-20 mA
output, if any, fluctuations when the flow rate varies in the process.
Ten attenuation levels, from 0 (means no attenuation) to 9 (maximum
attenuation of the fluctuations) are available.
Table 4: Response times of the current output and the display
depending on the filter chosen
Filter N° Response time (10% up to 90%)
0 300 ms
1 1,5 s
2 3 s
3 (by default) 5 s
4 7 s
5 11 s
6 20 s