Manual

When
using a surge pipe in a vessel, inuences from vessel
installations and turbulences can be excluded. Under these prereq-
uisites, the measurement of products with low dielectric values
r
value 1.6) is possible. In very adhesive products, measurement in a
surge pipe is not recommended.
Fig. 18: Conguration surge pipe
1 Radar sensor
2 Marking of the polarisation direction
3 Thread or ange on the instrument
4 Vent hole
5 Holes
6 Weld joint
7 Welding neck ange
8 Ball valve with complete opening
9 Fastening of the surge pipe
Instructions for orientation:
l Note marking of the polarisation plane on the sensor
l With threaded tting, the marking is on the hexagon, with ange
connection between the two ange holes
l All holes in the surge pipe must be in one plane with this marking
Instructions for the measurement:
Measu
rement in a surge
pipe
20 LEVEL TRANSMITTER 8136 4 20 mA/HART - two-wire
4 Mounting
41783-EN-120316