Manual

The real product level during this adjustment is not important, because
the min./max. adjustment is always carried out without changing the
product level. These settings can be made ahead of time without the
instrument having to be installed.
Proceed as follows:
1 Select the menu item "Setup" with [->] and conrm with [OK]. Now
select with [->] the menu item "Min. adjustment" and conrm with
[OK].
2 Edit the percentage value with [OK] and set the cursor to the
requested position with [->].
3 Set the requested percentage value with [+] and save with [OK].
The cursor jumps now to the distance value.
4 Enter the suitable distance value in m for the empty vessel (e.g.
distance from the sensor to the vessel bottom) corresponding to
the percentage value.
5 Save settings with [OK] and move with [ESC] and [->] to the max.
adjustment.
Proceed as follows:
1 Select with [->] the menu item max. adjustment and conrm with
[OK].
2 Prepare the percentage value for editing with [OK] and set the
cursor to the requested position with [->].
Setup/Min. adjustment
Set
up/Max. adjustment
38 LEVEL TRANSMITTER 8136 4 20 mA/HART - two-wire
6 Set up with the indicating and adjustment module
41783-EN-120316