Adjustment and commissioning
HIGH: Choose the value of the high switching threshold of the output.
INVERT: Invert the output or not.
DELAY: Choose the value of the time-out before switching for each digital output. This is valid for both output 
thresholds. Switching is only done if one of the thresholds, high or low (functions "High" or "Low"), is exceeded 
for a duration longer than this time-out.
Configuring in "Window" operating
The output status changes as soon as any threshold (low or high) is reached..
ON 
OFF 
contact
Low High
process input ("PV")
not inverted
ON 
OFF 
contact
Low High
process input ("PV")
inverted
Figure 64 :  Window operating
PV: Choose the process input associated with the output selected.
LOW: Choose the value of the process input for the low switching threshold of the output.
HIGH: Choose the value of the process input for the high switching threshold of the output.
INVERT: Invert the output or not.
DELAY: Choose the value of the time-out before switching for each output. This is valid for both output 
thresholds. Switching is only done if one of the thresholds, high or low (functions "High" or "Low"), is exceeded 
for a duration longer than this time-out.
Configuring in "FastPWM" operating
This mode is used to control a proportional solenoid valve.
T1
T2
0
1
T1
T1 T1
T2 T2
t
not inverted
output
inverted
output
T1
T2
T1 T1
T2 T2
t
0
1
T2 = period, constant = 1/frequency
T1 varies
Figure 65 :  "FastPWM" operating
PV: Choose the process input associated with the output selected.
LOW: Choose the value of the process input ("PV") corresponding to 0% PWM.
HIGH: Choose the value of the process input ("PV") corresponding to 100 % PWM.
INVERT: Invert the output or not.
FREQUENCY: Choose the value of the output frequency (= 1/T2), from 2 to 2000 Hz.