Instruction Manual
mxCONTROL Type 8620
Page 127
Processdata and Data Logging
Display-Presentation Displayed data
Abbre-
viation
(menu)
Full
Screen
Trend
chart
Line
Data-
Log.
Notes
Process value PV
x x x x
Set point SP
x x x
Set point vs. Process value SP/PV
x
Module output CMD
x x x
Alarm Maximum Output Timer
x x
displayed only, if
MOT enabled and
expired;
Data log in Module
output
Parameter (Code Level: Operator)
Parameter
Abbrevia-
tion
(menu)
Value range
Default values
(after successful download of
Cfg-File)
Sample Time Tsample 0.05/0.1 … 60.0 s 0.2 s
Set point SP Scal- …Scal+ of the assigned input Scal- + ((Scal+ - Scal-) /2)
Gain/amplification factor Kp 0.001 … 9999.0 (in % / unit) 10.0
Reset time Tn 0.1 … 9999.0 s 9999.0 s
Lower output limit Lim- 0.0 … Lim+ 0.0 %
Upper output limit Lim+ Lim- … 100.0 % 100.0 %
Safety output value CMDsafe 0.0 … 100.0 % 0.0%
Maximum output timer (MOT)
Maximum output time (*) +Tm 1 ... 10800 s 10800 s
(*) will be only displayed if the parameter “MOT” is configured as “Yes” in the menu „Configuration“
Configuration (Code Level: Specialist)
Configuration
Access
via
Cfg.-
menu
Access
via XML-
Cfg.-File
Abbreviation
(menu)
Value range
Default values
(after factory reset or
at start of Cfg-File-
Download)
Module active/not active rw rw Module On/Off Off
Inversion module sense
of action
rw rw InvMod Yes / No No
System switch override rw rw SSOR Yes / No No
Flow switch override rw rw FSOR Yes / No No
Maximum Output Timer rw rw MOT Yes / No No