10 Password Protection
Three authorization levels (CodeLevel) are provided for the operation of „Type 8620 mxCONTROL“:
General access, access for operators, access for specialists.
A password is a 4 digit number. The operator has to enter the password of the required protection
level in order to enter protected menus or menu items.
The specialist password also overrides the operator password.
A separate description on how to change the password is provided below.
Following user operations are password protected – see also table below:
Editing parameters / configuration data
Download/upload of parameter/configuration files
User calibration of 4-20mA outputs
Changing passwords
Factory Reset
Software Reset
Data Logging
Clock setting
Protection
Level
User Notes
0
General
access
Generell/normal process level:
Current process and control outputs are displayed.
Following actions are allowed:
Changing the operating mode of the „Type 8620 mxCONTROL“ between
automatic and manual mode.
Changing values in manual mode
Acknowledgement of Alarms (e.g. Maximum Output Timer) and messages.
Operating Language
Display-Mode
1
Operator
(Factory
set:
Code: 0001)
In addition to protection level 0 the following actions are allowed:
Parameter access
Up- and Download of parameter files
Data Logging
Setting Up Real Time Clock
2
Specialist
(Factory
set:
Code: 0002)
In addition to protection levels 0 and 1 the following actions are allowed:
Configuration access
Up- and Download of configuration files
User calibration of 4-20mA outputs
Changing Passwords
Factory Reset
Software Reset
Table 5: Password protection – different levels
Note! The "Master" password cannot be changed. The user of this password is granted
access to all protected code levels. This Master Password is available at Bürkert Service.