Instruction Manual
mxCONTROL Type 8620
Page 41
Parameter (CodeLevel: Operator)
Parameter
Access via
Datalog-
menu
Access via
XML-
Param.-File
Abbre-
viation
(menu)
Range
Default values
(after factory reset or at
start of Param-File-
Download)
Datalog Logging SD-Card rw -- -- enable/disable
Disable (only after
factory reset)
Sample Time rw rw Tsample 10 ... 99999sec 3600sec (*)
Logfile
Current log file name r -- Current -- --
Increase log file index by
one (Creates new log file)
w --
New
Logfile
-- --
Automatic log file size
limitation
rw rw FSizeLimit Yes / No No
Max. log file size rw rw FSizeMax 0.1 … 100.0 MB 1.0 MB
(*) Default value also after successful download of Cfg-File
Configuration (CodeLevel: Specialist)
Configuration
Access
via
Datalog-
menu
Access
via XML-
Cfg.-File
Abbrevia-
tion
(menu)
Value range
Default values
(after factory reset or
at start of Cfg-File-
Download)
Log File
Log file index (**) rw -- LFI 1 … 65535
1 (only after factory
reset)
EventLog
Event Log function rw rw EventLog On, Off On
Log Events (*)
Alarms rw rw Alarms On, Off On
Important error messages rw rw ErrorMsg On, Off On
Switching Operational
Mode
rw rw OpMode On, Off On
Switching of On/Off
outputs
rw rw O/O outputs On, Off On
Communication events /
errors
rw rw Comm On, Off On
Miscellaneous rw rw Misc On, Off On
(*) Only displayed, if Event Log function was set to On.
(**) Only displayed, if Datalogging was disabled