Function overview
PC Tool menu item Explanation
Connection
One connection possible at one time.
Connection … Establishing / closing a connection to a device.
Devices with Ethernet option: The user has to input IP address and the port number of
the desired device.
An integrated address book function supports easy device access.
Device data … Display of current device ID & serial number, Firmware ID & revision
Login
Device login window with selectable login level (Operator / Specialist / Master) and code
input.
Logout Device logout.
Remote Control
Current device display is shown in the PC-Tool, too. Navigation with keys like standing
directly in front of the device, including code input for accessing code protected menus.
Device keys have priority. Yellow LED displays operation mode / alarm status.
Download
(PC-> Device)
Download corresponding file from PC into device.
Corresponding device login level required:
Configuration file Specialist or higher
Parameter file Operator or higher
Upload
(Device->PC)
Upload corresponding file from device to PC
Corresponding device login level required:
Configuration file Specialist or higher
Parameter file Operator or higher
(Data)Log file Operator or higher
Upload of complete file or of a special time selection.
Remote deletion of (data)log file on SD Card possible (CodeLevel: Specialist).
For deletion of current datalog file, data logging needs to be disabled.
Service
Corresponding device login level required:
Download calibration file Master
Upload calibration file Master