Manual
36
Pin 4: CAN_H
Pin 5: CAN_L
Pin 1: Drain
Pin 3: V–
Pin 2: V+
View of plug from the front onto the pins:
Pin Signal Color
1 Drain
(shield)
2 V+ red
3 V- black
4 CAN_H white
5 CAN_L blue
An external initiator can be 
connected using the small 
3-pin terminal strip - see 
manual, chapter „Connection 
of an external initiator“.
english
37
Network Topology11.6. 
When installing a DeviceNet system, ensure that the termi-
nating circuit of the data lines is correct. The circuit prevents 
the occurrence of interference caused by signals refl ected 
onto the data lines. 
The trunk line must be terminated at both ends with 
resistors of 120 
Ω and 1/4 W power loss (see the manual, 
chapter „Network Topology of a DeviceNet System“).
Confi guring the Baud rate 11.7. 
and DVN address
8 DIP switches are available for confi guration:
DIP switches 1 to 6  for DeviceNet address• 
(factory setting:    63, i.e. DIP 1 - 6: on)
DIP switches 7 to 8  for Baud rate• 
(factory setting:   125, i.e. DIP 7 + 8: off)
Further confi guring - see manual, chapter „Confi guring the 
DeviceNet address / baud rate“
english
38
Confi guration of Process Data11.8. 
To transmit process data via an I/O connection, 2 static 
input and 1 static output assembly can be selected, see 
manual, chapter “Confi guration of Process Data” 
„Address“ in the table describes the data attribute of the 
assemblies for read access (class, instance, attributes).
Input-
Assemblies
Address Format of the Data attribute
value 0: OFF / value 1: ON
S1…S4 
(factory 
setting)
4, 1, 3 Byte 0:
Bit 0: position S1
Bit 1: position S2
Bit 2: position S3
Bit 3: position S4
S1…S4 + 
POS
(with POS: 
current 
position)
4, 2, 3 Byte 0:
Bit 0: position S1
Bit 1: position S2
Bit 2: position S3
Bit 3: position S4
Bit 4…7: not used
Byte 1:
POS in mm
„Address“ in the table describes the data attribute of the 
assemblies for read access (class, instance, attributes).
english
39
Output-
Assembly
Address Format of the Data attribute
value 0: OFF / value 1: ON
Solenoid 
valve 
SV 1 ... 3
4, 21, 3 Byte 0:
Bit 0: SV1
Bit 1: SV2
Bit 2: SV3
Bit 3…7: not used
  Confi guration of the Safety 11.9. 
Position of Solenoid Valves if 
Bus Error
If the bus fails, the solenoid valve is switched to a program-
mable safety position (factory setting: the solenoid valve 
is in the power-off-state) - for details see manual, chapter 
„Confi guration of the device“.
The bus status LED „Network“ on the electronic module 
specifi es the kind of error by color and blinking pattern - for 
details see manual, chapter „Display of the Status LEDs in 
the event of a bus error“).